ELKO, NV —
OSHA Inspection: BUREAU OF LAND MANAGEMENT - ELKO DISTRICT FIRE OFFICE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BUREAU OF LAND MANAGEMENT - ELKO DISTRICT FIRE OFFICE in 3900 EAST IDAHO STREET, ELKO, NV 89801 (NAICS 924110). OSHA activity number 342056157.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 3900 EAST IDAHO STREET
- City
- ELKO
- State
- NV
- ZIP
- 89801
- Mailing
- 3900 EAST IDAHO STREET, ELKO, NV 89801
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924110
- Employees
- 30
- Ownership type
- D
Citations
7 citations on file for this inspection.
1910.23 E01
- Issued
- Apr 21, 2017
- Abate by
- May 17, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(e)(1): Standard railings did not consist of a top rail, intermediate rails and posts, and/or did not have a vertical height of 42 inches nominal from the upper surface of the top rail to the floor, platform or runway: (a) Elko District Fire Office, Warehouse, South Stairs: Employees were exposed to a fall hazard of up to ten feet to the floor below while using a stairway on the dock with fourteen risers that is missing the standard railing with an approximate ten-inch gap between the steps and wire cage. (b) Elko District Fire Office, Warehouse, North Stairs: Employees were exposed to a fall hazard of up to ten feet to the floor below while using a stairway on the dock with fourteen risers that is missing the standard railing with an approximate nine-inch gap between the steps and wire cage.
Recent events (1)
- — Z (S) $0
1910.37 B01
- Issued
- Apr 21, 2017
- Abate by
- May 17, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(1): Each exit route was not adequately lighted so that an employee with normal vision can see along the exit route: (a) Men's Room: Employees were exposed to entrapment hazards in the event of a fire due to the Dual-Lite emergency lights being inoperable. (b) Women's Room: Employees were exposed to entrapment hazards in the event of a fire due to the emergency light with remote head capability emergency lights being inoperable. (c) Exit Hallway: Employees were exposed to entrapment hazards in the event of a fire due to the emergency light not being provided.
Recent events (1)
- — Z (S) $0
1910.305 B01
- Issued
- Apr 21, 2017
- Abate by
- May 17, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1): Openings through which conductors enter boxes, cabinets, or fittings were not effectively closed: (a) Fire Boiler Room: Employees are exposed to electric shock/fire hazards with open electrical panel spaces on panel C. THE U. S. DEPARTMENT OF INTERIOR, BUREAU OF LAND MANAGEMENT WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 1154521, CITATION 01, ITEM NUMBER 002 AND WAS AFFIRMED AS A FINAL ORDER ON OCTOBER 26, 2016, WITH RESPECT TO A WORKPLACE LOCATED AT BUREAU OF LAND MANAGEMENT, 3405 WHITE LAKE PARKWAY, RENO, NEVADA 89508.
Recent events (1)
- — Z (R) $0
1910.305 B02 I
- Issued
- Apr 21, 2017
- Abate by
- May 17, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: (a) Assistant Fire Management Office: Employees are exposed to electric shock/fire hazards with electrical outlet missing a faceplate and exposed electrical wiring. THE DEPARTMENT OF THE INTERIOR, BUREAU OF LAND MANAGEMENT WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 513138, CITATION 01, ITEM NUMBER 005 AND WAS AFFIRMED AS A FINAL ORDER ON December 11, 2012 WITH RESPECT TO A WORKPLACE LOCATED AT BUREAU OF LAND MANAGEMENT - TUSCARORA FIELD OFFICE, 3900 EAST IDAHO STREET, ELKO, NEVADA 89801.
Recent events (1)
- — Z (R) $0
1910.305 G01 IV A
- Issued
- Apr 21, 2017
- Abate by
- May 17, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) General Warehouse: Employees are exposed to electric shock/fire hazards by using a flexible cord attached to unknown electrical in roof crawl space. (b) General Warehouse: Employees are exposed to electric shock/fire hazards by using a flexible cord with light attachments while wrapped around electrical conduit. THE U. S. DEPARTMENT OF INTERIOR, BUREAU OF LAND MANAGEMENT WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 1154521, CITATION 02, ITEM NUMBER 004 AND WAS AFFIRMED AS A FINAL ORDER ON OCTOBER 26, 2016, WITH RESPECT TO A WORKPLACE LOCATED AT BUREAU OF LAND MANAGEMENT, 3405 WHITE LAKE PARKWAY, RENO, NEVADA 89508.
Recent events (1)
- — Z (R) $0
1910.305 G01 IV C
- Issued
- Apr 21, 2017
- Abate by
- May 17, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were used where run through doorways, windows, or similar openings: (a) General Warehouse: Employees are exposed to electric shock/fire hazards by using a flexible cord attached to unknown electrical which is run through door to roof crawl space. THE U. S. DEPARTMENT OF INTERIOR, BUREAU OF LAND MANAGEMENT WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 1155473, CITATION 01, ITEM NUMBER 002 AND WAS AFFIRMED AS A FINAL ORDER ON OCTOBER 26, 2016, WITH RESPECT TO A WORKPLACE LOCATED AT BUREAU OF LAND MANAGEMENT, 5665 MORGAN HILL ROAD, CARSON CITY, NEVADA 89701.
Recent events (1)
- — Z (R) $0
1910.305 J02 IV
- Issued
- Apr 21, 2017
- Abate by
- May 17, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: (a) Fire Warehouse: Employees were exposed to electric shock/fire hazards due to an electrical outlet connected to a Maytag 3000 Series Washer that was not protected by GFCI. THE U. S. DEPARTMENT OF INTERIOR, BUREAU OF LAND MANAGEMENT WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 1086132, CITATION 01, ITEM NUMBER 003 AND WAS AFFIRMED AS A FINAL ORDER ON NOVEMBER 10, 2015, WITH RESPECT TO A WORKPLACE LOCATED AT BUREAU OF LAND MANAGEMENT, 1 BLACK CANYON ROAD, ESSEX, CALIFORNIA 92332.
Recent events (1)
- — Z (R) $0
More inspections at Bureau of Land Management - Elko District Fire Office
View Bureau of Land Management - Elko District Fire Office's full OSHA safety record →
More inspections in this industry (NAICS 924110)
More inspections in NV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342056157.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.