Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MILITARY DELI BAKERY SERVICES, INC.

Programmed Related inspection · Safety discipline

On , OSHA opened a programmed Related safety inspection of MILITARY DELI BAKERY SERVICES, INC. in 531 SHAW DRIVE, SHAW A F B, SC 29152 (NAICS 722515). OSHA activity number 342111341.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Military Deli Bakery Services, INC. — free Get an email when a new federal OSHA severe-injury report for Military Deli Bakery Services, INC. is published. One employer, no account, unsubscribe in one click.
Site address
531 SHAW DRIVE
City
SHAW A F B
State
SC
ZIP
29152
Mailing
3600 THAYER COURT SUITE 100, AURORA, IL 60504
Inspection type
Programmed Related (J)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
722515
Employees
10
Ownership type
A

2 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 2 instances 10 exposed
Issued
Mar 10, 2017
Penalty
Initial $4,155 · Current $1,200 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    a) West wall of the Deli Area: A "Fellows" relocatable power tap listed for use with low powered loads such as computers, printers, T.V.s, radios, etc. was instead used to provide power to high powered loads, such as an Emerson microwave oven. The power tap , also listed to be "relocatable" was found to be secured to a metal cart with plastic band ties, which would require a tool such as a knife or scissors to remove.     b) East wall of the Supervisor's Office Area: A "Triplite" relocatable power tap used in the area was listed as "relocatable", but was found to be secured to a wall mounted wire basket with plastic band ties which would require a tool such as a knife or scissors to remove.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $4155

1910.304 B04

Serious Gravity 1 1 instance 10 exposed
Issued
Mar 10, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(4): Outlet devices had an ampere rating less than the load being served.  a) West wall of the Deli Area: A "Fellows" relocatable power tap rated to serve 15 amperes had the following items plugged into the device; An Emersion microwave oven 13.5 amps; Airmaster KopyKake 1.3 amps; Epson printer 1 amp; Computer 1.5 amps; a, and a scanner 1.5 amps a total of 18.3 amps. This was above the 15 amp rating.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Military Deli Bakery Services, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342111341.