Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DEFENSE COMMISSARY AGENCY WHIDBEY NAS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEFENSE COMMISSARY AGENCY WHIDBEY NAS in 2090 NORTH CORAL SEA BLD 2742, OAK HARBOR, WA 98278 (NAICS 445110). OSHA activity number 342121159.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Defense Commissary Agency Whidbey NAS — free Get an email when a new federal OSHA severe-injury report for Defense Commissary Agency Whidbey NAS is published. One employer, no account, unsubscribe in one click.
Site address
2090 NORTH CORAL SEA BLD 2742
City
OAK HARBOR
State
WA
ZIP
98278
Mailing
2090 NORTH CORAL SEA, BLD 2742, OAK HARBOR, WA 98278
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
445110
Employees
72
Ownership type
D

5 citations on file for this inspection.

1910.303 B02

Repeat Gravity 1 3 instances 72 exposed
Issued
Mar 9, 2017
Abate by
Apr 25, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling:    a) Facility, where electrical equipment not used as listed or labeled included:   1. Meat Department Change and Supply Room, where a relocatable power tap was used to supply power to appliances including, the Mr. Coffee drip coffee pot. (Item Corrected)   2. Carry Out Personnel Break Room, where relocatable power taps were used to supply power to appliances including, the GE microwave oven, the Hamilton Beach microwave oven, and the Oster Toaster oven. (Item Corrected)   3. Administrative Cubicle, where the Eaton uninterrupted power source (UPS) relocatable power tap, the Leviton relocatable power tap and the Ace relocatable power tap were daisy chained and used to supply power to computer equipment.  The Defense Commissary Agency was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 1169973, citation number 1, item number 1 and was affirmed as a final order on September 28, 2016 with respect to a workplace located at Marysville, WA.  The Defense Commissary Agency was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 1122685, citation number 1, item number 1 and was affirmed as a final order on April 8, 2016 with respect to a workplace located at Joint Base Lewis Mc Chord, WA.
Recent events (1)
  • — Z (R) $0

1910.303 G01 II

Repeat Gravity 1 3 instances 72 exposed
Issued
Mar 9, 2017
Abate by
Apr 25, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage:   a) Facility, where space located in front of electrical panels used for storage included:  1. Cashier Office, where items including two filing cabinets, books, and a telephone were stored in front of circuit panel CR.  2. Server Room, where items including boxes containing toner cartridges, empty cardboard boxes, and mailing packages were stored in front of circuit panels GG Left, GG Right, and CRI.  3. Battery Charging Area, where the Encore Floor Scrubber was stored in front of circuit panel FF.   The Defense Commissary Agency was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(g)(1)(ii), which was contained in OSHA inspection number 1122685, citation number 2, item number 1 and was affirmed as a final order on April 8, 2016 with respect to a workplace located at Joint Base Lewis Mc Chord, WA.
Recent events (1)
  • — Z (R) $0

1910.36 G02

Other-than-serious 1 instance 72 exposed
Issued
Mar 9, 2017
Abate by
Apr 25, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:  a) Carry Out Personnel Break Room, where the placement of the lockers and a chair reduced the aisle way width to 24 inches.
Recent events (1)
  • — Z (O) $0

1910.157 E02

Other-than-serious 5 instances 72 exposed
Issued
Mar 9, 2017
Abate by
Apr 25, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  a) Facility, where fire extinguishers not intended for employee use not inspected on a monthly basis included, but not limited to:   1. Vendor Door, where the Amerex Fire extinguisher was equipped with a tag dated 9/2.  2. Shipping and Receiving, where the Simplex Grinnell Fire extinguisher was equipped with a tag dated 9/2.   3. Yale Forklifts, where the Ansul Sentry fire extinguishers were equipped with tags dated 9/2.  4. Loading dock Break Room, where the Amerex Fire extinguisher was equipped with a tag dated 9/2.   5. Deli Bakery, where the Amerex Fire extinguisher was equipped with a tag dated 6/21.
Recent events (1)
  • — Z (O) $0

1910.305 G01 IV A

Other-than-serious 1 instance 72 exposed
Issued
Mar 9, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure:   a) Receiving Office, where an extension cord was used to supply power to the telephone and two printers.
Recent events (1)
  • — Z (O) $0

View Defense Commissary Agency Whidbey NAS's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342121159.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.