SEABROOK, NH —
OSHA Inspection: NEW ENGLAND PARTS WAREHOUSE, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of NEW ENGLAND PARTS WAREHOUSE, INC. in 239 WALTON ROAD, SEABROOK, NH 03874 (NAICS 423120). OSHA activity number 342137569.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NEW ENGLAND PARTS WAREHOUSE, INC.
- Site address
- 239 WALTON ROAD
- City
- SEABROOK
- State
- NH
- ZIP
- 03874
- Mailing
- 239 WALTON ROAD, SEABROOK, NH 03874
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423120
- Employees
- 40
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.36 D01
- Issued
- May 10, 2017
- Abate by
- May 16, 2017
- Penalty
- Initial $6,338 · Current $1,900 Reduced
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: a. The office emergency exit staircase - On or about February 23, 2017, the exit door in the staircase utilized by the office staff for emergency exit was locked from the outside, preventing the door from being used during emergency events.
Recent events (2)
- — I (S) $1900
- — Z (S) $6338
1910.37 B02
- Issued
- May 10, 2017
- Abate by
- May 16, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit.": Instance a. Back parking lot - On or about February 23, 2017, the exit door was not provided with a sign to indicate that it was an emergency exit. Instance b. Warehouse - On or about February 23, 2017, the exit door was not provided with a sign to indicate that it was an emergency exit.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B03 II
- Issued
- May 10, 2017
- Abate by
- May 16, 2017
- Penalty
- Initial $8,365 · Current $279 Reduced
General-duty citation text
29 CFR 1910.305(b)(3)(ii): Boxes shall be closed by suitable covers securely fastened in place: a. Warehouse - On or about February 23, 2017, the electrical outlet box utilized for powering the building's exterior lighting was not provided with a cover securely fastened in place. New England Parts Warehouse, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.305(b)(1)(ii), which was contained in OSHA inspection number 1140527, citation number 2, item number 4, and was affirmed as a final order on May 16, 2016, with respect to a workplace located at 239 Walton Rd, Seabrook, NH.
Recent events (2)
- — I (R) $279
- — Z (R) $8365
1910.37 B06
- Issued
- May 10, 2017
- Abate by
- May 16, 2017
- Penalty
- Initial $279 · Current $279
General-duty citation text
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color: Instance a. Drive-in bay area - On or about February 23, 2017, the emergency exit door signage was not illuminated. Instance b. BB3 bay door - On or about February 23, 2017, the emergency exit door signage was not illuminated. Instance c. Warehouse main entry - On or about February 23, 2017, the emergency exit door signage was not illuminated. Instance d. Annex building - On or about February 23, 2017, both of the emergency exit doors signs in this building were not illuminated. New England Parts Warehouse, Inc. was previously cited for violation of this Occupational Safety and Health standard or its equivalent standard 1910.37(b)(6), which was contained in OSHA inspection number 1140527, citation number 1, item number 2b, and was affirmed as a final order on May 16, 2016, with respect to a workplace located at 239 Walton Rd., Seabrook, NH.
Recent events (2)
- — I (R) $279
- — Z (R) $279
1910.110 F02 II
- Issued
- May 10, 2017
- Abate by
- May 16, 2017
- Penalty
- Initial $279 · Current $279
General-duty citation text
29 CFR 1910.110(f)(2)(ii): Liquefied petroleum gas container(s) stored inside were located near exits, stairways, or in areas normally used or intended for the safe exit of people: a. North East end exit door - On or about February 23, 2017, the propane tanks utilized for the forklifts were stored in the emergency exit passageway. New England Parts Warehouse, Inc. was previously cited for violation of this Occupational Safety and Health standard or its equivalent standard 1910.110 (f)(2)(ii), which was contained in OSHA inspection number 1140527, citation number 1, item number 2c, and was affirmed as a final order on May 16, 2016, with respect to a workplace located at 239 Walton Rd., Seabrook, NH.
Recent events (2)
- — I (R) $279
- — Z (R) $279
More inspections at NEW England Parts Warehouse, INC.
View NEW England Parts Warehouse, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 423120)
More inspections in NH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342137569.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.