OSHA Inspection: NEW ENGLAND PARTS WAREHOUSE, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of NEW ENGLAND PARTS WAREHOUSE, INC. in 239 WALTON ROAD, SEABROOK, NH 03874 (NAICS 423120). OSHA activity number 342137569.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch NEW England Parts Warehouse, INC. — free Get an email when a new federal OSHA severe-injury report for NEW England Parts Warehouse, INC. is published. One employer, no account, unsubscribe in one click.
Site address
239 WALTON ROAD
City
SEABROOK
State
NH
ZIP
03874
Mailing
239 WALTON ROAD, SEABROOK, NH 03874
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423120
Employees
40
Ownership type
A

5 citations on file for this inspection.

1910.36 D01

Serious Gravity 5 1 instance 5 exposed
Issued
May 10, 2017
Abate by
May 16, 2017
Penalty
Initial $6,338 · Current $1,900 Reduced
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:     a. The office emergency exit staircase - On or about February 23, 2017, the exit door in the staircase utilized by the office staff for emergency exit was locked from the outside, preventing the door from being used during emergency events.
Recent events (2)
  • — I (S) $1900
  • — Z (S) $6338

1910.37 B02

Serious Gravity 5 2 instances 10 exposed
Issued
May 10, 2017
Abate by
May 16, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit.":  Instance a. Back parking lot - On or about February 23, 2017, the exit door was not provided with a sign to indicate that it was an emergency exit.  Instance b. Warehouse - On or about February 23, 2017, the exit door was not provided with a sign to indicate that it was an emergency exit.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B03 II

Repeat Gravity 1 1 instance 10 exposed
Issued
May 10, 2017
Abate by
May 16, 2017
Penalty
Initial $8,365 · Current $279 Reduced
29 CFR 1910.305(b)(3)(ii): Boxes shall be closed by suitable covers securely fastened in place:    a. Warehouse - On or about February 23, 2017, the electrical outlet box utilized for powering the building's exterior lighting was not provided with a cover securely fastened in place.    New England Parts Warehouse, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.305(b)(1)(ii), which was contained in OSHA inspection number 1140527, citation number 2, item number 4, and was affirmed as a final order on May 16, 2016, with respect to a workplace located at 239 Walton Rd, Seabrook, NH.
Recent events (2)
  • — I (R) $279
  • — Z (R) $8365

1910.37 B06

Repeat 4 instances 12 exposed
Issued
May 10, 2017
Abate by
May 16, 2017
Penalty
Initial $279 · Current $279
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:    Instance a. Drive-in bay area - On or about February 23, 2017, the emergency exit door signage was not   illuminated.     Instance b. BB3 bay door - On or about February 23, 2017, the emergency exit door signage was not illuminated.    Instance c. Warehouse main entry - On or about February 23, 2017, the emergency exit door signage was not illuminated.    Instance d. Annex building - On or about February 23, 2017, both of the emergency exit doors signs in this building were not illuminated.    New England Parts Warehouse, Inc. was previously cited for violation of this Occupational Safety and Health standard or its equivalent standard 1910.37(b)(6), which was contained in OSHA inspection number 1140527, citation number 1, item number 2b, and was affirmed as a final order on May 16, 2016, with respect to a workplace located at 239 Walton Rd., Seabrook, NH.
Recent events (2)
  • — I (R) $279
  • — Z (R) $279

1910.110 F02 II

Repeat 1 instance 12 exposed
Issued
May 10, 2017
Abate by
May 16, 2017
Penalty
Initial $279 · Current $279
29 CFR 1910.110(f)(2)(ii): Liquefied petroleum gas container(s) stored inside were located near exits, stairways, or in areas normally used or intended for the safe exit of people:  a. North East end exit door - On or about February 23, 2017, the propane tanks utilized for the forklifts were stored in the emergency exit passageway.  New England Parts Warehouse, Inc. was previously cited for violation of this Occupational Safety and Health standard or its equivalent standard 1910.110 (f)(2)(ii), which was contained in OSHA inspection number 1140527, citation number 1, item number 2c, and was affirmed as a final order on May 16, 2016, with respect to a workplace located at 239 Walton Rd., Seabrook, NH.
Recent events (2)
  • — I (R) $279
  • — Z (R) $279

View NEW England Parts Warehouse, INC.'s full OSHA safety record →