CONCORD, CA —
OSHA Inspection: TECH SYSTEMS INC.
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of TECH SYSTEMS INC. in MILITARY OCEAN TERMINAL CONCORD PIER 3, CRANE #2, CONCORD, CA 94520 (NAICS 811310). OSHA activity number 342169240.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TECH SYSTEMS INC.
- Site address
- MILITARY OCEAN TERMINAL CONCORD PIER 3, CRANE #2
- City
- CONCORD
- State
- CA
- ZIP
- 94520
- Mailing
- 6131 WALKER LANE, SUITE 120, ALEXANDRIA, VA 22310
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811310
- Employees
- 275
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.147 C04
- Issued
- Aug 30, 2017
- Abate by
- Nov 1, 2017
- Penalty
- Initial $12,675 · Current $9,506 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(I): Energy control program. The employer did not develop, document or utilized procedures for the control of potentially hazardous energy when employees are engaged in the activities covered by this section. Pier 3, Crane 2, Machine House: Crane heavy mechanics worked on various mechanical and electrical equipment inside the crane machine house including motors, wall mounted circuit panels, safety switches, hoist motors for bridge crane, floor standing high voltage equipment, mechanical hoists, and mechanical rotating cable spools.
Recent events (2)
- — I (S) $9506.25
- — Z (S) $12675
1910.147 C05 II B
- Issued
- Aug 30, 2017
- Abate by
- Nov 1, 2017
- Penalty
- Initial $12,675 · Current $9,506 Reduced
General-duty citation text
29 CFR 1910.147(c)(5)(ii)(B): Lockout and tagout devices were not standardized within the facility in at least one of the following criteria: color; shape; or size. Pier 3, Cranes #1 and #2: Mechanics used locks which were different sizes, shapes and colors to deactivate, disconnect, or otherwise render inoperative any stored electrical energy while work is being performed on facilities or equipment affected by that stored energy.
Recent events (2)
- — I (S) $9506.25
- — Z (S) $12675
1910.147 C07 I A
- Issued
- Aug 30, 2017
- Abate by
- Sep 26, 2017
- Penalty
- Initial $12,675 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(7)(i)(A): Authorized employee(s) did not receive training in the recognition of applicable hazardous energy sources, the type and magnitude of the energy available in the workplace, and the methods and means necessary for energy isolation. Pier 3, Crane 2, Machine House: Employees were exposed to hazards from moving parts such as mechanical hoists and rotating cable spools being inadvertently energized while working inside the cranes machine houses conducting preventive maintenance.
Recent events (2)
- — I (S) $0
- — Z (S) $12675
1910.332 B02
- Issued
- Aug 30, 2017
- Abate by
- Sep 26, 2017
- Penalty
- Initial $12,675 · Current $0 Reduced
General-duty citation text
29 CFR 1910.332(b)(2): Employees who are covered by paragraph (a) of this section but who are not qualified persons were not trained in and familiar with any electrically related safety practices not specifically addressed by 1910.331 through 1910.335 but which are necessary for their safety. Pier 3, Crane 2, Machine House: Prior to March 10, 2017, crane heavy equipment mechanics who maintained the Transformer Secondary Substation System (TSS) equipment removed filters and their frames which potentially exposed them to live 4160 volt bus bars inside the TSS that had not been locked out or tagged out. On March 10, 2017, a crane heavy equipment mechanic removed a rear panel cover of the Transformer Secondary Substation System (TSS) equipment near two energized 4160 volt mechanical bus bars. The TSS was not de-energized prior to the work. The mechanic contacted the bus bars and was electrocuted.
Recent events (2)
- — I (S) $0
- — Z (S) $12675
1910.333 A01
- Issued
- Aug 30, 2017
- Abate by
- Nov 1, 2017
- Penalty
- Initial $12,675 · Current $9,506 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not de-energized before the employee works on or near them: Pier 3, Crane 2, Machine House: On March 10, 2017, a crane heavy equipment mechanic removed a rear metal panel cover of the Transformer Secondary Substation System (TSS) equipment near two energized 4160 volts metallic bus bars. The TSS was not de-energized prior to the work, the mechanic contacted the bus bars and was electrocuted.
Recent events (2)
- — I (S) $9506.25
- — Z (S) $12675
1910.333 B02
- Issued
- Aug 30, 2017
- Abate by
- Sep 26, 2017
- Penalty
- Initial $12,675 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(b)(2): "Lockout and Tagging." While any employee is exposed to contact with parts of fixed electric equipment or circuits which have been de-energized, the circuits energizing the parts shall be locked out or tagged or both in accordance with the requirements of this paragraph. Pier 3, Crane 2, Machine House: On March 8 and March 9, 2017, crane heavy equipment mechanics performed maintenance on the Transformer Secondary Substation System (TSS) equipment exposing them to 4160 volt bus bars.
Recent events (2)
- — I (S) $0
- — Z (S) $12675
1910.335 A01 I
- Issued
- Aug 30, 2017
- Abate by
- Nov 1, 2017
- Penalty
- Initial $12,675 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards were not provided with, and did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: Pier 3, Crane 2, Machine House: The crane heavy equipment mechanics, while replacing filters on the Transformer Secondary Substation System (TSS) equipment were exposed to potential electrical hazards from the 4160 volt bus bars inside the TSS.
Recent events (2)
- — I (O) $0
- — Z (S) $12675
1910.335 A01 IV
- Issued
- Aug 30, 2017
- Abate by
- Sep 26, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(iv): Employees did not wear nonconductive head protection wherever there is a danger of head injury from electric shock or burns due to contact with exposed energized parts. Pier 3, Crane 2, Machine House: The crane heavy equipment mechanic worked around energized parts while he serviced the Transformer Secondary Substation System (TSS) equipment. The mechanic contacted the 4160 volt bus bars inside the TSS and was electrocuted.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 V
- Issued
- Aug 30, 2017
- Abate by
- Sep 26, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(v): Employees did not wear protective equipment for the eyes or face wherever there is danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion. Pier 3, Crane 2, Machine House: The crane heavy equipment mechanic worked around energized parts while he serviced the Transformer Secondary Substation System (TSS) equipment. The mechanic contacted the 4160 volt bus bars inside the TSS and was electrocuted.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A02 I
- Issued
- Aug 30, 2017
- Abate by
- Nov 1, 2017
- Penalty
- Initial $12,675 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment if the tools or handling equipment might make contact with such conductors or parts. If the insulating capability of insulated tools or handling equipment is subject to damage, the insulating material shall be protected: Pier 3, Crane 2, Machine House: Insulated tools were not provided to the crane heavy equipment mechanic who worked near energized parts while he serviced the Transformer Secondary Substation System (TSS) equipment. The mechanic contacted the 4160 volt bus bars inside the TSS and was electrocuted.
Recent events (2)
- — I (O) $0
- — Z (S) $12675
More inspections at Tech Systems INC.
View Tech Systems INC.'s full OSHA safety record →
More inspections in this industry (NAICS 811310)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342169240.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.