On , OSHA opened a referral safety inspection of NAVAL FACILITIES ENGINEERING COMMAND SOUTHWEST in BUILDING 3015 NAVAL AIR STATION, NAVAL BASE VENTURA COUNTY, POINT MUGU NAWC, CA 93042 (NAICS 928110). OSHA activity number 342197415.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Naval Facilities Engineering Command Southwest for free Get an email when a new federal OSHA severe-injury report for Naval Facilities Engineering Command Southwest is published. One employer, no account, unsubscribe in one click.
Site address
BUILDING 3015 NAVAL AIR STATION, NAVAL BASE VENTURA COUNTY
City
POINT MUGU NAWC
State
CA
ZIP
93042
Mailing
311 MAIN ROAD BUILDING 1, POINT MUGU NAWC, CA 93042
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
100
Ownership type
Federal government (D)

3 citations on file for this inspection.

1910.332 B01

Serious Gravity 5 1 instance 3 exposed
Issued
Jun 13, 2017
Abate by
Jun 30, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  Automatic Transfer Switch Panel in Building 3015: On March 24, 2017, employees were not familiar with all elements of the Electrical Safe Program. Employees were working in the presence of energized electrical components without de-energizing and/or did not apply individual locks in a group-lockout operation. Employee(s) were exposed to electrical shock hazards up to 480 volts.
Recent events (1)
  • · Z (S) $0

1910.333 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 13, 2017
Abate by
Jun 21, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not de-energized before the employee worked on or was near to them:  Automatic Transfer Switch Panel in Building 3015: On March 24, 2017, energized component(s) inside the panel, such as but not limited to the bus bar, were not de-energized prior to an employee working on the extension cables from the permanently mounted generator.  Employee(s) were exposed to electrical shock hazards up to 480 volts.
Recent events (1)
  • · Z (S) $0

1910.333 B02 III A

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 13, 2017
Abate by
Jun 21, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2)(iii)(A): A lock and a tag were not placed on each disconnecting means used to de-energize circuits and equipment on which work was to be performed:  Automatic Transfer Switch Panel in Building 3015: On March 24, 2017, each authorized employee working at the main breaker panel did not affix a personal lockout/tagout device prior to performing work, such as but not limited to landing cables, at the open panel. Employee(s) were exposed to electrical shock hazards up to 480 volts.