MANLIUS, NY —
OSHA Inspection: L. & J. G. STICKLEY, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of L. & J. G. STICKLEY, INC. in ONE STICKLEY DRIVE, MANLIUS, NY 13104 (NAICS 337122). OSHA activity number 342198843.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- L. & J. G. STICKLEY, INC.
- Site address
- ONE STICKLEY DRIVE
- City
- MANLIUS
- State
- NY
- ZIP
- 13104
- Mailing
- P. O. BOX 480, MANLIUS, NY 13104
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 337122
- Employees
- 950
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.36 H02
- Issued
- May 30, 2017
- Penalty
- Initial $4,617 · Current $2,770 Reduced
General-duty citation text
29 CFR 1910.36(h)(2): The outdoor exit route was not covered where snow and ice was likely to accumulate along the route: a) Exit route off boiler room, on or about 3/23/17: The outdoor exit route was not covered where snow and ice could accumulate. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $2770.2
- — Z (S) $4617
1910.107 B10
- Issued
- May 30, 2017
- Penalty
- Initial $6,157 · Current $3,694 Reduced
General-duty citation text
29 CFR 1910.107(b)(10): Transparent panels used for illumination of spray booth(s) did not effectively isolate the spraying area from the area in which the lighting unit(s) were located: a) Finishing Dept., on or about 3/23/17: The left transparent panel for the light fixture for spray booth #4 was cracked. b) Finishing Dept., on or about 3/23/17: The right transparent panel for the light fixture for spray booth #3 was not in position leaving an approximate 2 inch opening at the top of the booth.
Recent events (2)
- — I (S) $3694.2
- — Z (S) $6157
1910.107 G02
- Issued
- May 30, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(g)(2): All spraying areas were not kept as free from the accumulation of deposits of combustible residues as practical: a) Finishing Dept., on or about 3/23/17: There was a heavy accumulation of combustible residue in the right corner and on the right wall of the sealer booth #4 where Valspar sealer is sprayed. b) Finishing Dept., on or about 3/23/17: There was a heavy accumulation of combustible residue on the floors and right corner of the Nichols & Stone booth where Linen White lacquer sealer is sprayed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.212 A01
- Issued
- May 30, 2017
- Penalty
- Initial $12,675 · Current $7,605 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, pinch points, rotating parts, flying chips and sparks: a) Rough Mill, on or about 3/22/17: Pinch points and ingoing nip points on the infeed rollers for the Raimann ripsaw were not guarded. b) Rough Mill, on or about 3/22/17: Ingoing nip points on the infeed conveying belt and pulley for the Powermat moulder 1200 were not adequately guarded. c) Machine Sanding, on or about 3/23/17: Rotating spindle end and nut projection on a State vertical spindle sander were not guarded. d) Machine Sanding, on or about 3/23/17: Ingoing nip points on the return conveyor belts and pulleys drive for the Heesemann wide belt sander were not adequately guarded. e) Sample Shop, on or about 3/23/17: Rotating spindle end and nut projection on a Max vertical spindle sander were not guarded. f) Maintenance Shop, on or about 3/23/17: Rotating chuck on a Dayton 20 inch drill press was not guarded. g) Fine Mill, on or about 3/29/17: Pinch points created by the closing Plexiglas guards on the 246 Linear Shaper were not adequately guarded in that the two hand trips did not prevent access into the area.
Recent events (2)
- — I (S) $7605
- — Z (S) $12675
1910.304 G05
- Issued
- May 30, 2017
- Penalty
- Initial $6,157 · Current $3,694 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) Finishing Dept., on or about 3/23/17: A rheostat outlet box used to power a Dayton pedestal fan had no continuity to ground. b) Finishing Dept., on or about 3/23/17: A Dayton pedestal fan next to the Nichols & Stone booth was not grounded in that the ground pin was missing from the plug end. c) Trim Repair Area, on or about 3/23/17: A Dayton pedestal fan was not grounded in that the ground pin was missing from the plug end.
Recent events (2)
- — I (S) $3694.2
- — Z (S) $6157
1910.305 G01 IV A
- Issued
- May 30, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Finishing Dept., on or about 3/23/17: A strip outlet attached to a work cabinet near the top coat booth, powering a pedestal fan, was being used as permanent wiring. b) Finishing Dept., on or about 3/23/17: A rheostat outlet box with a Dayton pedestal fan plugged in, was being used as permanent wiring.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- May 30, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) Finishing Dept., on or about 3/23/17: Flexible cord providing current to a rheostat box and a flexible cord providing current to a Dayton pedestal fan were pulled loose from their plug fittings. b) Trim Repair Area, on or about 3/23/17: Flexible cord providing current to a rheostat box for the hot knife at the workbench, was pulled loose at the plug fitting.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- May 30, 2017
- Abate by
- Jul 3, 2017
- Penalty
- Initial $12,675 · Current $7,605 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a) Throughout the facility, on or about 3/23/17: Maintenance employees performing trouble shooting work on machines and equipment were not provided with hard hat, face shields, FR protective clothing, gloves, etc. Abatement documentation must be submitted for this item.
Recent events (2)
- — I (S) $7605
- — Z (S) $12675
1910.36 D01
- Issued
- May 30, 2017
- Abate by
- Jun 23, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(d)(1): Exit door(s) were locked. Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: a) Factory floor, main evacuation route, on or about 3/23/17: Two sets of double doors, both marked as an exit, each had the right side door locked at the top and bottom of the door. b) Main entrance to reception area, on or about 3/23/17: Two sets of double doors, both marked as an exit, each had the right side door locked at the top and bottom of the door. Abatement certification must be submitted for item b.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B01 II
- Issued
- May 30, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Rough Mill, on or about 3/22/17: Junction box along the gluing conveyor platform for the Doucet RT-100 gluing wheel did not have the unused openings effectively closed in that the knockouts on the box were pushed in.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at L. & J. G. Stickley, INC.
View L. & J. G. Stickley, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 337122)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342198843.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.