BOISE, ID —
OSHA Inspection: A-CORE OF BOISE, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of A-CORE OF BOISE, INC. in MICRON BUILDING #36, BOISE, ID 83716 (NAICS 238210). OSHA activity number 342228384.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- A-CORE OF BOISE, INC.
- Site address
- MICRON BUILDING #36
- City
- BOISE
- State
- ID
- ZIP
- 83716
- Mailing
- 6531 BUSINESS WAY, BOISE, ID 83716
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 14
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.403 B01
- Issued
- May 5, 2017
- Penalty
- Initial $12,548 · Current $0 Reduced
General-duty citation text
29 CFR 1926.403(b)(1): The employer did not ensure that electrical equipment is free from recognized hazards that are likely to cause death or serious physical harm to employees. a) On or about February 28, 2017, or prior thereto, A-Core of Boise, Inc. Office and Equipment Warehouse: A 10 gauge extension cord, or pigtail, was not tested for correct attachment of the grounding conductor. The L2 Hot and Grounding Conductor were reversed during installation. The pigtail was designed by A-Core of Boise, Inc. to be used with a Husqvarna Power Pack PP65, and a Husqvarna K6500 HF High Frequency Saw. b) On or about March 8, 2017, or prior thereto, First Healthy Choice Site: The grounding conductor and the L2 hot line on a 10 gauge extension cord, or pigtail, were reversed during concrete cutting work. c) On or about March 28, 2017 or prior thereto, Micron Technology Building #36: The grounding conductor and the L2 hot line on a 480 Volt 10 gauge extension cord, or pigtail, were reversed. This resulted in energizing the casing of the Husqvarna Power Pack PP 65 during concrete cutting work. NOTE: This item was corrected during the inspection.
Recent events (2)
- — I (S) $0
- — Z (S) $12548
1926.404 A03
- Issued
- May 5, 2017
- Penalty
- Initial $0 · Current $7,500
General-duty citation text
29 CFR 1926.404(a)(3): A grounding terminal or grounding-type device on a receptacle, cord connector, or attachment plug was used for purposes other than grounding. a) On or about March 8, 2017, or prior thereto, First Healthy Choice Site: The grounding conductor and the L2 hot line on a 10 gauge extension cord, or pigtail, were reversed during concrete cutting work. b) On or about March 28, 2017 or prior thereto, Micron Technology Building #36: The grounding conductor and the L2 hot line on a 480 Volt 10 gauge extension cord, or pigtail, were reversed. This resulted in energizing the casing of the Husqvarna Power Pack PP 65 during concrete cutting work. NOTE: This item was corrected during the inspection.
Recent events (2)
- — I (S) $7500
- — Z (S) $0
1926.404 F06
- Issued
- May 5, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, and enclosures was not permanent and continuous. a) On or about February 28, 2017, or prior thereto, A-Core of Boise, Inc. Office and Equipment Warehouse: A 10 gauge extension cord, or pigtail, was not tested for correct attachment of the grounding conductor. The L2 Hot and Grounding Conductor were reversed during installation. The pigtail was designed by A-Core of Boise, Inc. to be used with a Husqvarna Power Pack PP65, and a Husqvarna K6500 HF High Frequency Saw. b) On or about March 8, 2017, or prior thereto, First Healthy Choice Site: The grounding conductor and the L2 hot line on a 10 gauge extension cord, or pigtail, were reversed during concrete cutting work. c) On or about March 28, 2017 or prior thereto, Micron Technology Building #36: The grounding conductor and the L2 hot line on a 480 Volt 10 gauge extension cord, or pigtail, were reversed. This resulted in energizing the casing of the Husqvarna Power Pack PP 65 during concrete cutting work. NOTE: This item was corrected during the inspection.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at A-Core of Boise, INC.
View A-Core of Boise, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in ID
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342228384.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.