Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: OIL PATCH GROUP, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of OIL PATCH GROUP, INC. in LEASE COVINGTON 46 SEC 46 BLOCK 57 T1 WELL 10H, ORLA, TX 79770 (NAICS 213112). OSHA activity number 342246410.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch OIL Patch Group, INC. — free Get an email when a new federal OSHA severe-injury report for OIL Patch Group, INC. is published. One employer, no account, unsubscribe in one click.
Site address
LEASE COVINGTON 46 SEC 46 BLOCK 57 T1 WELL 10H
City
ORLA
State
TX
ZIP
79770
Mailing
11767 KATY FREEWAY, SUITE 510A, HOUSTON, TX 77079
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213112
Employees
162
Ownership type
A

5 citations on file for this inspection.

1910.305 B01 I

Serious Gravity 5 2 instances 3 exposed
Issued
Aug 15, 2017
Abate by
Aug 25, 2017
Penalty
Initial $7,619 · Current $7,619
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed.   On or about April 05, 2017, conductors entering the cutout box for an AC condenser units mount on mobile home trailers were not protected from abrasion and openings through which they enter were not effectively close in the following instances . This condition exposed employee to electrical hazards.  a. MH Trailer # OPR-1313- Mud Logger living quarters.  b. MH Trailer # OPR-1320- Company Hand living quarters.
Recent events (1)
  • — Z (S) $7619

1910.305 B01 II

Serious Gravity 1 1 instance 3 exposed
Issued
Aug 15, 2017
Abate by
Aug 25, 2017
Penalty
Initial $4,572 · Current $4,572
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   On or about April 05, 2017, a three phase 480volt to 208/120 volt step-down transformer mount onto the OPR-11613 trailer had two unprotected knock-out openings. This condition exposed employees to electrical shock hazards.
Recent events (1)
  • — Z (S) $4572

1910.304 G05

Repeat Gravity 1 1 instance 3 exposed
Issued
Aug 15, 2017
Abate by
Aug 25, 2017
Penalty
Initial $10,755 · Current $10,755
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures were not permanent, continuous, and effective.  Drilling Site: On or about April 05, 2017, the mud logger's trailer OPR-11313 was not properly grounded to earth. This condition exposed the employees to electrical shock hazards.  Oil Patch Group was previously cited for a violation of this occupational safety and health standard 29CFR1910.304(g)(5), which was contained in OSHA inspection number 1044481, citation number 01, item number 02 and was affirmed as a final order on 03/30/2015, with respect to a workplace located at Big E Rig No.4, 16.3 miles South of Pecos in Pecos TX. 79772.
Recent events (1)
  • — Z (R) $10755

1910.305 E01

Other-than-serious 1 instance 1 exposed
Issued
Aug 15, 2017
Abate by
Aug 25, 2017
Penalty
Initial $855 · Current $855
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations shall be installed so as to prevent moisture or water from entering and accumulating within the enclosures. The enclosures shall be weatherproof in wet locations.  On or about April 05, 2017, Mud Logger mobile home trailer OPR-1323 cut-off box installed in an area exposed to weather did not have weather proof cover. This condition exposed employees to electrical shock hazards.
Recent events (1)
  • — Z (O) $855

1910.305 J02 VI

Other-than-serious 3 instances 3 exposed
Issued
Aug 15, 2017
Abate by
Aug 25, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(2)(vi): A receptacle installed in a wet location where the product intended to be plugged into it is not attended while in use (for example, sprinkler system controllers, landscape lighting, and holiday lights) did not have an enclosure that is weatherproof with the attachment plug cap inserted or removed.  On or about April 05, 2017, Mud Engineer's mobile home trailer OPR-1128 receptacles installed in areas exposed to weather conditions did not have weather proof covers. This condition exposed employees to electrical shock hazards.
Recent events (1)
  • — Z (O) $0

View OIL Patch Group, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342246410.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.