OSHA Inspection: THE UNITED ILLUMINATING COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of THE UNITED ILLUMINATING COMPANY in 550 BOSTON POST RD., ORANGE, CT 06477 (NAICS 221121). OSHA activity number 342279130.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The United Illuminating Company — free Get an email when a new federal OSHA severe-injury report for The United Illuminating Company is published. One employer, no account, unsubscribe in one click.
Site address
550 BOSTON POST RD.
City
ORANGE
State
CT
ZIP
06477
Mailing
100 MARSH HILL ROAD, ORANGE, CT 06477
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221121
Employees
950
Ownership type
A

2 citations on file for this inspection.

1910.269 L08 V

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 1, 2017
Abate by
Jun 27, 2017
Penalty
Initial $12,675 · Current $8,800 Reduced
29 CFR 1910.269(l)(8)(v): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective clothing and other protective equipment that had an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2.    Worksite: The employer did not ensure that the employees required to work on or near energized electrical equipment were wearing appropriate types of personal protective equipment (PPE) at all times to protect from the hazard of electrical arc flash.      On or about 04/26/2017, one of employees sustained severe facial burns as the result of an arc flash/blast while performing tasks, such as (but not limited to) testing and replacing energized electric utility meters.
Recent events (2)
  • — I (S) $8800
  • — Z (S) $12675

1910.269 A02 I A

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Jun 1, 2017
Abate by
Jun 27, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.269(a)(2)(i)(A): Each employee was not trained in, and familiar with, the safety-related work practices, safety procedures, personal protective equipment, and other safety requirements in this section that pertain to his or her job assignments.    Worksite: The employer did not ensure that the employees who were required to work on or near energized electrical equipment/parts were trained in and familiar with the requirements for personal protective equipment related to the job tasks/assignments.      On or about 04/26/2017, one of employees performing tasks, such as (but not limited to) testing and replacing energized electric utility meters without wearing appropriate types of personal protective equipment (PPE) sustained severe facial burns as the result of an arc flash/blast.