LOUDONVILLE, NY —
OSHA Inspection: D.V. ELECTRIC INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of D.V. ELECTRIC INC. in VILLAGE AT SHAKER CREEK ROUTE 9, LOUDONVILLE, NY 12211 (NAICS 238210). OSHA activity number 342296001.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- D.V. ELECTRIC INC.
- Site address
- VILLAGE AT SHAKER CREEK ROUTE 9
- City
- LOUDONVILLE
- State
- NY
- ZIP
- 12211
- Mailing
- 1731 BROADWAY, SCHENECTADY, NY 12306
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 11
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.404 B01 I
- Issued
- May 4, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. (a) 4248 Cambridge Way, first floor, during electrical rough-in: Extension cord used to power a Ridgid R7122 mixing drill (used for boring) was connected to a 120V duplex receptacle (by panel box) that was not equipped with GFCI protection.
Recent events (1)
- — Z (O) $0
1926.416 E01
- Issued
- May 4, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.416(e)(1): Worn or frayed electric cords or cables were used: (a) 4248 Cambridge Way, first floor, during electrical rough-in: Extension cord used to power a Ridgid R7122 mixing drill (used for boring) was in use with a broken ground pin.
Recent events (1)
- — Z (O) $0
More inspections at D.V. Electric INC.