MILL HALL, PA ·
OSHA Inspection: RAGU INC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of RAGU INC in 31 HOSPITALITY LN, MILL HALL, PA 17751 (NAICS 721110). OSHA activity number 342343530.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RAGU INC
- Site address
- 31 HOSPITALITY LN
- City
- MILL HALL
- State
- PA
- ZIP
- 17751
- Mailing
- 31 HOSPITALITY LN, MILL HALL, PA 17751
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 21
- Ownership type
- Private (A)
Citations
6 citations on file for this inspection.
1910.147 C01
- Issued
- Jun 26, 2017
- Abate by
- Aug 11, 2017
- Penalty
- Initial $3,078 · Current $3,078
General-duty citation text
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative: a) Maintenance: The employer did not establish an energy control program (lockout/tagout) to ensure the safety of employees working on equipment including, but not limited to, compactor and electrical circuits and equipment, on or about May 22, 2017. Abatement Certification Required.
Recent events (1)
- · Z (S) $3078
1910.151 C
- Issued
- Jun 26, 2017
- Abate by
- Aug 11, 2017
- Penalty
- Initial $3,078 · Current $3,078
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a) Boiler room: Suitable facilities for quick flushing of eyes were not provided within the work area for employees using corrosive materials including, but not limited to, Calci-Solve, Chlorox Commercial Solutions and Liquid Scale Dissolver, as observed on or about May 22, 2017. Abatement Certification Required.
Recent events (1)
- · Z (S) $3078
1910.303 F02
- Issued
- Jun 26, 2017
- Abate by
- Aug 11, 2017
- Penalty
- Initial $1,847 · Current $1,847
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) Boiler room: The panel box located near the Navien water heater units was not legibly marked to indicate its purpose, as observed on or about May 22, 2017. Abatement Certification Required.
Recent events (1)
- · Z (S) $1847
1910.305 B01 II
- Issued
- Jun 26, 2017
- Abate by
- Aug 11, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Boiler room: Unused openings in two panel boards were not effectively closed, as observed on or about May 22, 2017. Abatement Certification Required.
Recent events (1)
- · Z (S) $0
1910.305 B02 I
- Issued
- Jun 26, 2017
- Abate by
- Aug 11, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: a) Boiler room: Electrical junction boxes (2) were not provided with covers approved for the purpose, as observed on or about May 22, 2017. b) Boiler room: The cover to the electrical conduit/wireway beneath the panel boards had been removed and not replaced, as observed on or about May 22, 2017. Abatement Certification Required.
Recent events (1)
- · Z (S) $0
1910.333 A01
- Issued
- Jun 26, 2017
- Abate by
- Aug 11, 2017
- Penalty
- Initial $3,078 · Current $3,078
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them: a) Boiler room: The Navien water heating systems were not de-energized prior to an employee working on or near them, on or about May 22, 2017. Abatement Certification Required.
Recent events (1)
- · Z (S) $3078
More inspections in this industry (NAICS 721110)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 342343530.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.