SEATTLE, WA —
OSHA Inspection: ARMY CORPS OF ENGINEERS SEATTLE DISTRICT OFFICE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ARMY CORPS OF ENGINEERS SEATTLE DISTRICT OFFICE in 4735 E. MARGINAL WAY SOUTH BUILDING 1202, SEATTLE, WA 98134 (NAICS 541330). OSHA activity number 342351327.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ARMY CORPS OF ENGINEERS SEATTLE DISTRICT OFFICE
- Site address
- 4735 E. MARGINAL WAY SOUTH BUILDING 1202
- City
- SEATTLE
- State
- WA
- ZIP
- 98134
- Mailing
- 4735 E. MARGINAL WAY SOUTH BUILDING 1202, SEATTLE, WA 98134
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 541330
- Employees
- 472
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.303 B02
- Issued
- Aug 2, 2017
- Abate by
- Aug 14, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Room 1570; A Makita model HG11 heat gun rated at 12.5 amps was plugged into a surge protector power strip (relocatable power tap). CORRECTED DURING INSPECTION (b) Suite 1680 Center of Room; A temporary server was plugged into an surge protector power strip which was plugged into another surge protector power strip (daisy chained). (c) Suite 1680 Cubicle adjacent to door; A surge protector power strip was plugged into another surge protector power strip (daisy chained), which powered desktop computer equipment. CORRECTED DURING INSPECTION (d) Suite 1680 corner cubicle in adjacent room; A power strip was plugged into a yellow extension cord which was plugged into another surge protector power strip (daisy chain), which powered a tandem charger, power supply and iphone. CORRECTED DURING INSPECTION (e) Room 2660; An Ovente Kettle and Belkin white toaster were plugged into a surge protector power strip. CORRECTED DURING INSPECTION (f) Room 2662; A white surge protector power strip was plugged into another white surge protector power strip (daisy chain) which powered desktop computer equipment. (g) Cubicle 297; A white surge protector power strip was plugged into another white surge protector power strip (daisy chain) which powered desktop computer equipment. CORRECTED DURING INSPECTION (h) Cadet Creek Conference Room; A white surge protector power strip was plugged into another white surge protector power strip which powered a Dell laptop. CORRECTED DURING INSPECTION The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances. This exposes employees to possible electrical fire hazards.
Recent events (1)
- — Z (S) $0
1910.305 B02 I
- Issued
- Aug 2, 2017
- Abate by
- Aug 21, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: a) Furniture Warehouse; A junction box underneath a breaker panel was missing a cover, exposing employees to live electrical wires and possible electrical shock hazards.
Recent events (1)
- — Z (S) $0
1904.40 A
- Issued
- Aug 2, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1904.40(a): The employer did not provide an authorized government representative the records within the four business hours: a) The employer did not provide copies of requested OSHA 300 logs and 300A Summary forms (for 2014, 2015, 2016 and year to date 2017) within four business hours.
Recent events (1)
- — Z (O) $0
More inspections at Army Corps of Engineers Seattle District Office
View Army Corps of Engineers Seattle District Office's full OSHA safety record →