OSHA Inspection: ITZ ELECTRIC, INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of ITZ ELECTRIC, INC. in 3341 LOOP 534, KERRVILLE, TX 78028 (NAICS 238210). OSHA activity number 342355013.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ITZ Electric, INC. — free Get an email when a new federal OSHA severe-injury report for ITZ Electric, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
ITZ ELECTRIC, INC.
Site address
3341 LOOP 534
City
KERRVILLE
State
TX
ZIP
78028
Mailing
804 EAST MAIN STREET, FREDERICKSBURG, TX 78624
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
5
Ownership type
A

3 citations on file for this inspection.

1926.403 B01 II

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 12, 2017
Abate by
Jun 16, 2017
Penalty
Initial $3,802 · Current $3,200 Reduced
29 CFR 1926.403(b)(1)(ii): Safety of equipment was not determined on the basis of mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided:    On or about May 25, 2017, and in times prior thereto, a job made dead front was attached to the face of a breaker panel with black tape, located at the opening to the construction site.  This condition exposed workers to the hazard to electric burns in the event the metal sheet created a short circuit.
Recent events (2)
  • — I (S) $3200
  • — Z (S) $3802

1926.404 F06

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 12, 2017
Abate by
Jun 16, 2017
Penalty
Initial $6,338 · Current $6,300 Reduced
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous:    On or about May 25, 2017, and in times prior thereto, the temporary power breaker panel was installed without a grounding buss.  The panel was located in front of the construction site and exposed workers to the hazard of electric shock.
Recent events (2)
  • — I (S) $6300
  • — Z (S) $6338

1926.405 G02 IV

Serious Gravity 5 2 instances 5 exposed
Issued
Jun 12, 2017
Abate by
Jun 16, 2017
Penalty
Initial $6,338 · Current $0 Reduced
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws:    On or about May 25,  2017, and in times prior thereto, the conductors entering temporary breaker panel were not fitted with a strain relief device.  This condition exposed workers to an electrical hazard, located at:    a:  Main power pole  b:  In front of construction site
Recent events (2)
  • — I (S) $0
  • — Z (S) $6338

View ITZ Electric, INC.'s full OSHA safety record →