Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FERGUSON ELECTRIC CONSTRUCTION COMPANY, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of FERGUSON ELECTRIC CONSTRUCTION COMPANY, INC. in 78 SAWYER AVENUE, TONAWANDA, NY 14150 (NAICS 238210). OSHA activity number 342360559.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ferguson Electric Construction Company, INC. — free Get an email when a new federal OSHA severe-injury report for Ferguson Electric Construction Company, INC. is published. One employer, no account, unsubscribe in one click.
Site address
78 SAWYER AVENUE
City
TONAWANDA
State
NY
ZIP
14150
Mailing
333 ELLICOTT STREET, BUFFALO, NY 14203
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
4
Ownership type
A

3 citations on file for this inspection.

1910.269 C04 II B

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Nov 17, 2017
Abate by
Jan 4, 2018
Penalty
Initial $12,675 · Current $0 Reduced
29 CFR 1910.269(c)(4)(ii)(B): The employee could not be expected to recognize and avoid the hazards involved in the job and a more extensive briefing was not held;    a) On or about 05/18/17 at the PerOxychem substation located at 78 Sawyer Avenue, Tonawanda, New York; employees were performing preventative maintenance on the breakers in the substation. While preparing to work on breaker #6, an employee contacted live equipment and suffered burns and fractures. The breaker # 6 was energized differently than the 3 previous breakers that were serviced the day before. A secondary or redundant source of energy was present and was not discussed with the specific differences or procedures prior to work commencing.    ABATEMENT DOCUMENTATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $12675

1910.269 M03 II

Serious Gravity 10 1 instance 2 exposed
Issued
Nov 17, 2017
Penalty
Initial $12,675 · Current $0 Reduced
29 CFR 1910.269(m)(3)(ii): The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be denenergized were open.  The employer did not render such means inoperable, unless its design does not so permit, and then sure that such means are tagged to indicate that employees are at work:    a) On or about 05/18/17 at the PerOxychem substation located at 78 Sawyer Avenue, Tonawanda, New York; employees were performing preventative maintenance on the breakers in the substation. While preparing to work on breaker #6, an employee contacted live equipment and suffered burns and fractures. Switch #10 was left closed causing a backfeed from breaker #2 to breaker #6.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $12675

1910.269 M03 VI

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Nov 17, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.269(m)(3)(vi): 29 CFR 1910.269(m)(3)(vi): After the applicable requirements in paragraphs (m)(3)(i) through (m)(3)(v) of this section have been followed and the system operator gives a clearance to the employee in charge, the employer did not ensure that the lines and equipment are deenergized by testing the lines and equipment to be worked with a device designed to detect voltage:  a) On or about 05/18/17 at the PerOxychem substation located at 78 Sawyer Avenue, Tonawanda, New York; employees were performing preventative maintenance on the breakers in the substation. While preparing to work on breaker #6, an employee contacted live equipment and suffered burns and fractures. The equipment was not tested prior to beginning work to ensure it was deenergized.  NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Ferguson Electric Construction Company, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342360559.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.