SANDWICH, IL ·
OSHA Inspection: LEVEL PRECISION CONSTRUCTION LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of LEVEL PRECISION CONSTRUCTION LLC in 413 EAST HALL STREET, SANDWICH, IL 60548 (NAICS 238310). OSHA activity number 342365491.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LEVEL PRECISION CONSTRUCTION LLC
- Site address
- 413 EAST HALL STREET
- City
- SANDWICH
- State
- IL
- ZIP
- 60548
- Mailing
- 3607 ORCHARD DRIVE, HAMMOND, IN 46323
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238310
- Employees
- 5
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.405 D
- Issued
- Jul 25, 2017
- Penalty
- Initial $2,716 · Current $1,901 Reduced
General-duty citation text
29 CFR 1926.405(d): Switchboards and panelboards. Switchboards that have any exposed live parts shall be located in permanently dry locations and accessible only to qualified persons. Panelboards shall be mounted in cabinets, cutout boxes, or enclosures designed for the purpose and shall be dead front. However, panelboards other than the dead front externally-operable type are permitted where accessible only to qualified persons. Exposed blades of knife switches shall be dead when open. a. On or about May 31, 2017, at the above referenced worksite, employees engaged in commercial construction activities were working in close proximity to an improperly covered panel. Employees were thereby exposed to electrical shock. There is no abatement certification of documentation required for this item.
Recent events (2)
- · I (S) $1901.2
- · Z (S) $2716
1926.405 A02 II F
- Issued
- Jul 25, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(F): Temporary lights shall not be suspended by their electric cords unless cords and lights are designed for this means of suspension. a. On or about May 31, 2017, at the above referenced worksite, employees engaged in commercial construction activities were working in close proximity to overhead temporary lighting that was suspended by their electrical cord(s). The lighting was in use / energized at the time of inspection. Employees were thereby exposed to electrical shock. There is no abatement certification of documentation required for this item.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1926.405 A02 II E
- Issued
- Jul 25, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(E): All lamps for general illumination shall be protected from accidental contact or breakage. Metal-case sockets shall be grounded. a. On or about May 31, 2017, at the above referenced worksite, employees engaged in commercial construction activities were working in close proximity to overhead temporary lighting that was not protected from breakage. The lighting was in use / energized at the time of inspection. Employees were thereby exposed to electrical shock while walking and working in the area. There is no abatement certification of documentation required for this item.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1926.20 B02
- Issued
- Jul 25, 2017
- Abate by
- Aug 15, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.20(b)(2): The employer did not initiate and maintain programs which provided for frequent and regular inspections of the job site, materials and equipment to be made by a competent person(s): a. On or about May 31, 2017, at the above addressed jobsite, safety inspections were not made by competent persons capable of identifying and correcting those hazards which could result in employee injuries. Employees were thereby exposed to falls and electrical hazards at this jobsite. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(c).
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections in this industry (NAICS 238310)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342365491.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.