STREAMWOOD, IL ·
OSHA Inspection: FRESH EXPRESS INCORPORATED
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of FRESH EXPRESS INCORPORATED in 1109 E. LAKE STREET, STREAMWOOD, IL 60107 (NAICS 311999). OSHA activity number 342375649.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FRESH EXPRESS INCORPORATED
- Site address
- 1109 E. LAKE STREET
- City
- STREAMWOOD
- State
- IL
- ZIP
- 60107
- Mailing
- 1109 E. LAKE STREET, STREAMWOOD, IL 60107
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311999
- Employees
- 700
- Ownership type
- Private (A)
Citations
1 citation on file for this inspection.
1910.119 D03 II
- Issued
- Sep 28, 2017
- Abate by
- Nov 27, 2017
- Penalty
- Initial $11,408 · Current $6,845 Reduced
0170
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices. (a) Fresh Express Incorporated, at 1109 E. Lake Street, Streamwood, Illinois: On or about June 5, 2017, the employer failed to determine and document that the anhydrous ammonia refrigeration system was adequately designed, installed, and maintained to protect employees from an uncontrolled release of anhydrous ammonia in compliance with recognized and generally accepted good engineering practices (RAGAGEP). The evaporator condenser containing (EV-12) anhydrous ammonia in the pack out area was installed unprotected, immediately adjacent to the mezzanine used by powered industrial trucks. Anhydrous ammonia was released on June 5, 2017 when the unprotected evaporator condenser (EV-12) was struck by a powered industrial truck delivering materials to the mezzanine area. Among other methods, a feasible abatement method to correct this hazard is to ensure that the ammonia refrigeration system is adequately designed, installed, and maintained in compliance with a RAGAGEP such as the ANSI/ASHRAE-15 2016, Safety Standard for Refrigeration Systems, Section 11.1 General Restrictions - Safeguards: "Means shall be taken to adequately safeguard piping, controls, and other refrigerating equipment to minimize possible accidental damage or rupture by external sources."
Recent events (2)
- · I (S) $6845
- · Z (S) $11408
More inspections at Fresh Express Incorporated
View Fresh Express Incorporated's full OSHA safety record →
More inspections in this industry (NAICS 311999)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 342375649.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.