OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Busch Products INC. — free Get an email when a new federal OSHA severe-injury report for Busch Products INC. is published. One employer, no account, unsubscribe in one click.
Establishment
BUSCH PRODUCTS INC.
Site address
110 BAKER STREET
City
SYRACUSE
State
NY
ZIP
13206
Mailing
110 BAKER STREET, SYRACUSE, NY 13206
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327991
Employees
94
Ownership type
A

3 citations on file for this inspection.

1910.151 C

Serious Gravity 1 1 instance 1 exposed
Issued
Jul 20, 2017
Penalty
Initial $2,747 · Current $2,060 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:     a)  Filter Press Area, on or about 6/15/17: No eyewash was in close proximity for employees working with Aries 1024  a corrosive material containing: sodium hydroxide.
Recent events (2)
  • — I (S) $2060.25
  • — Z (S) $2747

1910.157 E03

Serious Gravity 1 1 instance 3 exposed
Issued
Jul 20, 2017
Penalty
Initial $2,747 · Current $2,060 Reduced
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:   a) Throughout the facility, on or about 6/15/17:  Several portable fire extinguishers did not have annual inspections, last inspection conducted was June 2012.
Recent events (2)
  • — I (S) $2060.25
  • — Z (S) $2747

1910.304 G05

Other-than-serious 1 instance 2 exposed
Issued
Jul 20, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous and effective:   a) Inventory Room, on or about 6/15/17: A B800 Alienbees Light, path to ground was not permanent and continuous.