MINNEAPOLIS, MN —
OSHA Inspection: U.S. DEPARTMENT OF VETERANS AFFAIRS, VETERANS HEALTH ADMIN, MINNEAPOLIS VA HEALTH CARE SYSTEM
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. DEPARTMENT OF VETERANS AFFAIRS, VETERANS HEALTH ADMIN, MINNEAPOLIS VA HEALTH CARE SYSTEM in ONE VETERANS DRIVE, MINNEAPOLIS, MN 55417 (NAICS 622110). OSHA activity number 342386380.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. DEPARTMENT OF VETERANS AFFAIRS, VETERANS HEALTH ADMIN, MINNEAPOLIS VA HEALTH CARE SYSTEM
- Site address
- ONE VETERANS DRIVE
- City
- MINNEAPOLIS
- State
- MN
- ZIP
- 55417
- Mailing
- ONE VETERANS DRIVE, MINNEAPOLIS, MN 55417
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 3800
- Ownership type
- D
Citations
12 citations on file for this inspection.
1910.178 L01 II
- Issued
- Aug 18, 2017
- Abate by
- Aug 30, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(1)(ii) as required by 29 CFR 1960.8(b): The employer did not ensure that each operator had successfully completed the training required by paragraph (l), except as permitted by paragraph (l)(5), prior to permitting an employee to operate a powered industrial truck: (a) Energy Center; An operator of the Mitsubishi, Model T15B470M, hydraulic lift, S.N. 07807, has not been trained.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.212 A01
- Issued
- Aug 18, 2017
- Abate by
- Sep 1, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(1) as required by 29 CFR 1960.8(b): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: (a) Garage; South Bend Precision Lathe, Catalog No. CL81874B, was used on metal round stock without a guard to protect the operator from the rotating chuck and flying chips. (b) Furniture Repair; Sears Craftsman 17" drill press, Model No. 113.213170, was used without a guard for the rotating chuck and drill bit.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.212 A03 II
- Issued
- Aug 18, 2017
- Abate by
- Sep 1, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(3)(ii) as required by 29 CFR 1960.8(b): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s): (a) Garage; Barker Engineering Co. horizontal milling machine, CMR # 132 ME, 618 EE2408, was used on metal stock without a guard to protect the operator from the rotating bit.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.219 D01
- Issued
- Aug 18, 2017
- Abate by
- Sep 1, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(d)(1) as required by 29 CFR 1960.8(b): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o): (a) Garage; Barker Engineering Co. horizontal milling machine, CMR # 132 ME, 618 EE2408, was used on metal stock without a guard to protect the operator from the rotating pulley(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.219 E01 I
- Issued
- Aug 18, 2017
- Abate by
- Sep 1, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(e)(1)(i) as required by 29 CFR 1960.8(b): Horizontal belts which had both runs seven feet or less from the floor level were not guarded with a guard that extended to at least fifteen inches above the belt: (a) Garage; Barker Engineering Co. horizontal milling machine, CMR # 132 ME, 618 EE2408, was used on metal stock without a guard to protect the operator from the rotating belt(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Aug 18, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2) as required by 29 CFR 1960.8(b): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Prosthetics, wheelchair lab; A metal 4-plex receptacle box was mounted to a shelving unit/workbench and was powered by an orange flexible cord.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Aug 18, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A) as required by 29 CFR 1960.8(b): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) Prosthetics, wheelchair lab; A metal 4-plex receptacle box was mounted to a shelving unit/workbench and was powered by an orange flexible cord.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01
- Issued
- Aug 18, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1) as required by 29 CFR 1960.8(b): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: (a) AC Shoot; A coffee maker and a cart containing a coffee grinder and other items were located in front of a circuit breaker panel labeled NLBM1-7, thereby blocking access to the panel.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.304 B04
- Issued
- Aug 18, 2017
- Abate by
- Aug 30, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(4) as required by 29 CFR 1960.8(b): Outlet devices had an ampere rating less than the load being served: (a) Garage; A refrigerator, microwave oven, and toaster were plugged into a relocatable power tap, a.k.a. power strip. (b) Energy Center, control room; A refrigerator and two microwave ovens were plugged into a relocatable power tap, a.k.a. power strip.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Aug 18, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii) as required by 29 CFR 1960.8(b): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: (a) Prosthetics, wheelchair lab; The outer insulation on a hand-held drill was detached from the drill housing, exposing the inner wires to being pulled.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.253 B04 III
- Issued
- Aug 18, 2017
- Abate by
- Aug 30, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(iii) as required by 29 CFR 1960.8(b): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: (a) ATS, closet BC-105a; Smith Equipment Tag-A-Long portable torch outfit was stored with small oxygen and acetylene cylinders connected and positioned together.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 B01 II
- Issued
- Aug 18, 2017
- Abate by
- Aug 30, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(1)(ii) as required by 29 CFR 1960.8(b): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided: (a) Plumbing shop; Circuit breaker panel labeled NLBM1-8 has a broken latch causing the door to stay open. (b) AC Shoot; Circuit breaker panel labeled NLBM1-7 has a broken latch causing the door to stay open.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at U.S. Department of Veterans Affairs, Veterans Health Admin, Minneapolis VA Health Care System
More inspections in this industry (NAICS 622110)
More inspections in MN
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342386380.