HEREFORD, TX —
OSHA Inspection: CAVINESS BEEF PACKERS, LTD
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of CAVINESS BEEF PACKERS, LTD in 3255 W. HIGHWAY 60, HEREFORD, TX 79045 (NAICS 311611). OSHA activity number 342390499.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CAVINESS BEEF PACKERS, LTD
- Site address
- 3255 W. HIGHWAY 60
- City
- HEREFORD
- State
- TX
- ZIP
- 79045
- Mailing
- P.O. BOX 790, HEREFORD, TX 79045
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311611
- Employees
- 709
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.147 C04 II
- Issued
- Nov 14, 2017
- Abate by
- Dec 11, 2017
- Penalty
- Initial $12,675 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(ii): Procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, 29 CFR 1910.147(c)(4)(ii)(A), (c)(4)(ii)(B), (c)(4)(ii)(C) and (c)(4)(ii)(D): On or about June 3, 2017, the employer energy control procedures for the booster station #1 did not clearly outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy where employees were exposed to electrical hazards.
Recent events (3)
- — F (S) $0
- — C (S) $12675
- — Z (S) $12675
1910.332 B02
- Issued
- Nov 14, 2017
- Abate by
- Dec 11, 2017
- Penalty
- Initial $12,675 · Current $0 Reduced
General-duty citation text
29 CFR 1910.332(b)(2): Employees, who were not qualified persons, were not trained in and familiar with any electrically related safety practices not specifically addressed by 29 CFR 1910.331 through 29 CFR 1910.335, but which were necessary for their safety. On or about June 3, 2017, the employer did not ensure employees performing trouble shooting work on electrical panels were qualified electricians trained to work on electrical equipment and exposed them to electrical shock hazards.
Recent events (3)
- — F (S) $0
- — C (S) $12675
- — Z (S) $12675
1910.333 A
- Issued
- Nov 14, 2017
- Abate by
- Dec 11, 2017
- Penalty
- Initial $12,675 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized: On or about June2, 2017, the employer did not ensure safety-related work practices were used to prevent electric shock while employees were trouble shooting the electric panel for booster station #1 and exposed them to electric shock hazards.
Recent events (3)
- — F (S) $0
- — C (S) $12675
- — Z (S) $12675
1910.333 B02 III
- Issued
- Nov 14, 2017
- Abate by
- Dec 11, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(iii): A lock and a tag was not placed on each disconnecting means used to de-energize circuits and equipment on which work is to be performed, except as provided in paragraphs (b)(2)(iii)(C) and (b)(2)(iii)(E) of this section: On or about June 2, 2017, the employer did not ensure employees trouble shooting an electrical panel box for booster station #1 pump utilized a lock and tag on the disconnect and exposed them to electric shock hazards.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Nov 14, 2017
- Abate by
- Dec 11, 2017
- Penalty
- Initial $12,675 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: On or about June 2, 2017, the employer did not provide personal protective equipment, such as electrical gloves, to employees trouble shooting the electrical panel box for booster station #1pump and exposed them to electric shock hazards.
Recent events (3)
- — F (S) $0
- — C (S) $12675
- — Z (S) $12675
More inspections at Caviness Beef Packers, LTD
View Caviness Beef Packers, LTD's full OSHA safety record →
More inspections in this industry (NAICS 311611)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342390499.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.