Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: BIA/WESTERN REGION/COLORADO RIVER AGENCY

Follow-up inspection · Health discipline

On , OSHA opened a follow-up health inspection of BIA/WESTERN REGION/COLORADO RIVER AGENCY in IRRIGATION MAINTENANCE 21051-3 EAST POSTON ROAD, POSTON, AZ 85371 (NAICS 921190). OSHA activity number 342399755.

Watch Bia/Western Region/Colorado River Agency — free Get an email when a new federal OSHA severe-injury report for Bia/Western Region/Colorado River Agency is published. One employer, no account, unsubscribe in one click.
Site address
IRRIGATION MAINTENANCE 21051-3 EAST POSTON ROAD
City
POSTON
State
AZ
ZIP
85371
Mailing
12124 1ST AVENUE, PARKER, AZ 85344
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
921190
Employees
83
Ownership type
D

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 1 instance 13 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Maintenance Shop, Poston, AZ: Employees were using a Porta Cool unit plugged into a series-connected extension cord and relocatable power tap (RPT). Per UL listing, RPTs are not to be series-connected to other RPTs or connected to extension cords. Employees were exposed to a potential fire hazard.
Recent events (1)
  • — Z (S) $0

1910.304 A02

Serious Gravity 5 1 instance 13 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(a)(2): Grounded conductors were attached to terminals or leads so as to reverse designated polarity:  Outside wall of the Maintenance Shop Office: The duplex receptacle supplying power to the Porta Cool unit was wired with reverse polarity. Employees were exposed to an electrical shock hazard.
Recent events (1)
  • — Z (S) $0

1910.334 A02 I

Serious Gravity 1 1 instance 13 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):  Maintenance Shop, Poston, AZ: The 100-foot yellow extension cord used to power the Porta Cool unit had a damaged outer jacket which exposed the inner conductors. Employees were exposed to a potential electrical shock hazard.
Recent events (1)
  • — Z (S) $0

View BIA/WESTERN REGION/COLORADO RIVER AGENCY's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342399755.