OSHA Inspection: VANTAGE PRODUCTS CORPORATION

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of VANTAGE PRODUCTS CORPORATION in 960 ALMON ROAD, COVINGTON, GA 30014 (NAICS 326199). OSHA activity number 342401015.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Vantage Products Corporation — free Get an email when a new federal OSHA severe-injury report for Vantage Products Corporation is published. One employer, no account, unsubscribe in one click.
Site address
960 ALMON ROAD
City
COVINGTON
State
GA
ZIP
30014
Mailing
960 ALMON ROAD, COVINGTON, GA 30014
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
59
Ownership type
A

3 citations on file for this inspection.

1910.333 A02

Serious Gravity 5 1 instance 3 exposed
Issued
Nov 21, 2017
Abate by
Dec 11, 2017
Penalty
Initial $5,926 · Current $3,556 Reduced
29 CFR 1910.333(a)(2): Where exposed live parts were not de-energized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices were not used to protect employees who could be exposed to the electrical hazards involved.  On or about June 15, 2017, maintenance and supervisory employees were exposed to electrical parts energized to 480 volts where the employees opened electrical panels on mold machines number 2 and number 4 to tap sticking mercury switches where other safety-related work practices were not used.
Recent events (2)
  • — I (S) $3555.6
  • — Z (S) $5926

1910.333 C02

Serious Gravity 5 1 instance 3 exposed
Issued
Nov 21, 2017
Abate by
Dec 11, 2017
Penalty
Initial $5,926 · Current $3,556 Reduced
29 CFR 1910.333(c)(2): Unqualified persons were allowed to work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section.  On or about June 15, 2017, maintenance and supervisory employees were exposed to live electrical parts energized to 480 volts where the employees were permitted to open electrical panels on mold machines number 2 and number 4 to tap sticking mercury switches and had not received electrical training from the employer to act as qualifies persons.
Recent events (2)
  • — I (S) $3555.6
  • — Z (S) $5926

1910.335 A01 I

Serious Gravity 5 1 instance 3 exposed
Issued
Nov 21, 2017
Abate by
Dec 11, 2017
Penalty
Initial $5,926 · Current $3,556 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed.  On or about June 15, 2017, maintenance and supervisory employees were exposed to live electrical parts energized to 480 volts where the employees were permitted to open electrical panels on mold machines number 2 and number 4 to tap sticking mercury switches using only safety glasses as personal protective equipment.
Recent events (2)
  • — I (S) $3555.6
  • — Z (S) $5926

View Vantage Products Corporation's full OSHA safety record →