OSHA Inspection: GLOBUS ELECTRIC, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of GLOBUS ELECTRIC, INC. in ONE AVENUE L, NEWARK, NJ 07105 (NAICS 238210). OSHA activity number 342409901.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Globus Electric, INC. for free Get an email when a new federal OSHA severe-injury report for Globus Electric, INC. is published. One employer, no account, unsubscribe in one click.
Site address
ONE AVENUE L
City
NEWARK
State
NJ
ZIP
07105
Mailing
1440 N. BROAD ST., HILLSIDE, NJ 07205
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
12
Ownership type
Private (A)

5 citations on file for this inspection.

1926.28 A

Serious Gravity 10 1 instance 3 exposed
Issued
Sep 29, 2017
Penalty
Initial $5,070 · Current $3,000 Reduced
29 CFR 1926.28(a): The employer did not require the wearing of appropriate personal protective equipment in all operations where there is an exposure to hazardous conditions:    a) One Avenue L, Newark, NJ 07105 - MCC 35N     Employees exposed to arc flash and shock hazards were not provided with Hazard Risk category (HRC) II  arc rated shirt and pants or coveralls while working on 480 volt energized live parts.   On 6/3/2017, an employee received second degree burns when an arc flash occurred.      Violation occurred on or about 6/3/2017
Recent events (2)
  • · I (S) $3000
  • · Z (S) $5070

1926.97 C02 VIII

Serious Gravity 10 1 instance 8 exposed
Issued
Sep 29, 2017
Abate by
Dec 20, 2017
Penalty
Initial $5,070 · Current $3,000 Reduced
29 CFR 1926.97(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table E-4 and Table E-5.    a) 1 Avenue L, Newark, NJ    Rubber insulating blankets were not tested every 12 months and Class II rubber insulating gloves were not testing every 6 months and after use, when used without protective gloves, in accordance with Table E-5.     Violation occurred on or about 6/3/2017
Recent events (2)
  • · I (S) $3000
  • · Z (S) $5070

1926.97 C02 VII

Serious Gravity 10 1 instance 3 exposed
Issued
Sep 29, 2017
Penalty
Initial $5,070 · Current $3,000 Reduced
29 CFR 1926.97(c)(2)(vii): The employer did not ensure that protector gloves were worn over insulating gloves:       a)  One Avenue L, Newark, NJ    Employees exposed to electric shock and arc flash hazards were not provided with protector gloves to be worn over their Cat II MaxiFlex insulating gloves.      Violation occurred on or about 6/3/2017
Recent events (2)
  • · I (S) $3000
  • · Z (S) $5070

1926.102 A01

Serious Gravity 10 1 instance 3 exposed
Issued
Sep 29, 2017
Penalty
Initial $5,070 · Current $3,000 Reduced
29 CFR 1926.102(a)(1): 29 CFR 1926.102(a)(1): The employer did not ensure that each affected employee used appropriate eye or face protection when exposed to eye or face hazards from flying particles, molten metal, liquid chemicals, acids or caustic liquids, chemical gases or vapors, or potentially injurious light radiation.    a)  One Avenue L, Newark, NJ    Employees exposed to arc flash hazards were not provided with HRC II arc rated face shield while working on 480 volt energized live parts, to protect against flying particles and molten metal.   On 6/3/2017, an employee received second degree burns when an arc flash occurred.     Violation occurred on or about 6/3/2017
Recent events (2)
  • · I (S) $3000
  • · Z (S) $5070

1926.416 A01

Serious Gravity 10 1 instance 3 exposed
Issued
Sep 29, 2017
Abate by
Dec 20, 2017
Penalty
Initial $5,070 · Current $3,000 Reduced
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:    a)  One Avenue L, Newark, NJ 07105 - MCC 35N    Employees did not effectively guard energized circuits while making power connection from 480 volt main switch gear to 1200 amp feeder/disconnect switch.  On 6/3/2017, an employee received second degree burns when an arc flash occurred.     Violation occurred on or about 6/3/2017
Recent events (2)
  • · I (S) $3000
  • · Z (S) $5070