OSHA Inspection: THE BEACH WATERPARK

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of THE BEACH WATERPARK in 2590 WATERPARK DRIVE, MASON, OH 45040 (NAICS 713110). OSHA activity number 342425816.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Beach Waterpark for free Get an email when a new federal OSHA severe-injury report for The Beach Waterpark is published. One employer, no account, unsubscribe in one click.
Establishment
THE BEACH WATERPARK
Site address
2590 WATERPARK DRIVE
City
MASON
State
OH
ZIP
45040
Mailing
2590 WATERPARK DRIVE, MASON, OH 45040
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
713110
Employees
250
Ownership type
Private (A)

5 citations on file for this inspection.

1910.303 G01

Serious Gravity 5 1 instance 6 exposed
Issued
Sep 7, 2017
Penalty
Initial $9,054 · Current $3,000 Reduced
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment.    a) Employer did not provide sufficient working space around electrical equipment, exposing employees to an electrical and a fire hazard.
Recent events (2)
  • · I (S) $3000
  • · Z (S) $9054

1910.303 G01 VII B

Serious Gravity 5 1 instance 5 exposed
Issued
Sep 7, 2017
Penalty
Initial $9,054 · Current $0 Reduced
29 CFR 1910.303(g)(1)(vii)(B): Outdoor electric equipment shall be installed in suitable enclosures and shall be protected from accidental contact by unauthorized personnel, or by vehicular traffic, or by accidental spillage or leakage from piping systems. No architectural appurtenance or other equipment may be located in the working space required by paragraph (g)(1)(i) of this section.    a) Employer did not provide outdoor electrical equipment with suitable enclosures to prevent employee exposure and the risk of fire.
Recent events (2)
  • · I (S) $0
  • · Z (S) $9054

1910.303 G02 I

Deleted Serious Gravity 5 1 instance 5 exposed
Issued
Sep 7, 2017
Penalty
Initial $9,054 · Current $0 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the following means:  a) In the pump area there were live electrical wires hanging from an open junction box exposing employees to contact with electrical hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $9054

1910.305 B01 II

Serious Gravity 5 1 instance 6 exposed
Issued
Sep 7, 2017
Penalty
Initial $9,054 · Current $3,000 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed.    a) The circuit breaker cabinet and the 480 electric control panel has unused openings, exposing employees to live electrical components.
Recent events (2)
  • · I (S) $3000
  • · Z (S) $9054

1910.303 F02

Other-than-serious 1 instance 6 exposed
Issued
Sep 7, 2017
Penalty
Initial $1,016 · Current $0 Reduced
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident.    a)Employer did not properly mark circuit breakers located in the maintenance building IAW 29 CFR 1910.303(f)(2).