FRESNO, CA ·
OSHA Inspection: U.S. DEPARTMENT OF VETERANS AFFAIRS -VA CENTRAL CALIFORNIA HEALTH CARE SYSTEM - FRESNO DIVISION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. DEPARTMENT OF VETERANS AFFAIRS -VA CENTRAL CALIFORNIA HEALTH CARE SYSTEM - FRESNO DIVISION in 2615 E. CLINTON AVENUE, FRESNO, CA 93703 (NAICS 622110). OSHA activity number 342509759.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. DEPARTMENT OF VETERANS AFFAIRS -VA CENTRAL CALIFORNIA HEALTH CARE SYSTEM - FRESNO DIVISION
- Site address
- 2615 E. CLINTON AVENUE
- City
- FRESNO
- State
- CA
- ZIP
- 93703
- Mailing
- 2615 E. CLINTON AVENUE DIRECTOR (00), FRESNO, CA 93703
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 3000
- Ownership type
- Federal government (D)
Citations
3 citations on file for this inspection.
1910.303 B02
- Issued
- Sep 6, 2017
- Abate by
- Oct 2, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling. Main Hospital Building, East Fifth Floor, Social Worker Office: A relocatable power strip was being used to power a small refrigerator, a microwave oven, a coffee maker and a fax machine. Employees were exposed to electrical shock hazards.
Recent events (1)
- · Z (S) $0
1910.305 B02 I
- Issued
- Sep 6, 2017
- Abate by
- Oct 2, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose. Machine Shop: A 2 inch x 4 inch pull box was not provided with a cover. The pull box house a live electrical conductors exposing employees to electrical hazards.
Recent events (1)
- · Z (S) $0
1910.303 G01
- Issued
- Sep 6, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Warehouse Bldg. 32, Lower Level: Panel WHB-B was blocked by wooden pallets and employees were unable to access the electrical equipment immediately.