Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,991Inspections Most recent open 2026-08-24 Last loaded 2026-08-27

OSHA Inspection: U.S. DEPARTMENT OF VETERANS AFFAIRS -VA CENTRAL CALIFORNIA HEALTH CARE SYSTEM - FRESNO DIVISION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. DEPARTMENT OF VETERANS AFFAIRS -VA CENTRAL CALIFORNIA HEALTH CARE SYSTEM - FRESNO DIVISION in 2615 E. CLINTON AVENUE, FRESNO, CA 93703 (NAICS 622110). OSHA activity number 342509759.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Department of Veterans Affairs -VA Central California Health Care System - Fresno Division for free Get an email when a new federal OSHA severe-injury report for U.S. Department of Veterans Affairs -VA Central California Health Care System - Fresno Division is published. One employer, no account, unsubscribe in one click.
Site address
2615 E. CLINTON AVENUE
City
FRESNO
State
CA
ZIP
93703
Mailing
2615 E. CLINTON AVENUE DIRECTOR (00), FRESNO, CA 93703
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
3000
Ownership type
Federal government (D)

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 2 instances 2 exposed
Issued
Sep 6, 2017
Abate by
Oct 2, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling.  Main Hospital Building, East Fifth Floor, Social Worker Office: A relocatable power strip was being used to power a small refrigerator, a microwave oven, a coffee maker and a fax machine.  Employees were exposed to electrical shock hazards.
Recent events (1)
  • · Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 1 exposed
Issued
Sep 6, 2017
Abate by
Oct 2, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose.  Machine Shop: A 2 inch x 4 inch pull box was not provided with a cover. The pull box house a live electrical conductors exposing employees to electrical hazards.
Recent events (1)
  • · Z (S) $0

1910.303 G01

Other-than-serious 1 instance 1 exposed
Issued
Sep 6, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:   Warehouse Bldg. 32, Lower Level: Panel WHB-B was blocked by wooden pallets and employees were unable to access the electrical equipment immediately.
Recent events (1)
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 342509759.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.