Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: IXPALIA, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of IXPALIA, INC. in 3800 PROMONTORY POINT DRIVE, AUSTIN, TX 78744 (NAICS 311830). OSHA activity number 342520160.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ixpalia, INC. — free Get an email when a new federal OSHA severe-injury report for Ixpalia, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
IXPALIA, INC.
Site address
3800 PROMONTORY POINT DRIVE
City
AUSTIN
State
TX
ZIP
78744
Mailing
P.O. BOX 17563, AUSTIN, TX 78766
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311830
Employees
120
Ownership type
A

9 citations on file for this inspection.

1910.212 A01

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 26, 2017
Abate by
Nov 9, 2017
Penalty
Initial $4,889 · Current $2,975 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    On or about August 3, 2017, and in times prior thereto, the chip tumbler's rotating drum was not guarded exposing employees to the hazards of being caught between the rotating tumbler and the frame of the machine in the production area.
Recent events (2)
  • — I (S) $2975
  • — Z (S) $4889

1910.215 B09

Serious Gravity 1 1 instance 1 exposed
Issued
Oct 26, 2017
Abate by
Nov 9, 2017
Penalty
Initial $4,889 · Current $2,975 Reduced
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:    On or about August 3, 2017, and in times prior thereto, the tongue guard on the bench grinder, located in the shop area, was out of adjustment, exposing employees to the hazards of being struck by flying particles of the grinding stone in the event of wheel breakage.
Recent events (2)
  • — I (S) $2975
  • — Z (S) $4889

1910.303 G01

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 26, 2017
Abate by
Nov 9, 2017
Penalty
Initial $4,889 · Current $2,975 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:    On or about August 3, 2017, and in times prior thereto, the area in front of Panels D and D2, located in the small mixer area and disconnect 1 in the outside air compressor area were used for storage.  This condition created an electrical hazard to workers at the establishment.
Recent events (2)
  • — I (S) $2975
  • — Z (S) $4889

1910.303 G02 II

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 26, 2017
Abate by
Nov 9, 2017
Penalty
Initial $4,889 · Current $2,975 Reduced
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage:    On or about August 3, 2017, and in times prior thereto, 240 volt electrical panel C was damaged by a forklift.  This created an electrical hazard to workers, located in the production area.
Recent events (2)
  • — I (S) $2975
  • — Z (S) $4889

1910.304 G05

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 26, 2017
Abate by
Nov 9, 2017
Penalty
Initial $4,889 · Current $2,975 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    On or about August 3, 2017, and in times prior thereto, The ground prong was missing on an red, three outlet extension cord, located in the small mixer area.
Recent events (2)
  • — I (S) $2975
  • — Z (S) $4889

1910.305 B01 II

Serious Gravity 5 2 instances 2 exposed
Issued
Oct 26, 2017
Abate by
Nov 9, 2017
Penalty
Initial $6,519 · Current $2,975 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    On or about August 3, 2017, and in times prior thereto, breaker blanks on panel E and a side knock out and panel C were missing.  The panels were located at the electrical area.
Recent events (2)
  • — I (S) $2975
  • — Z (S) $6519

1910.305 G01 IV C

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 26, 2017
Abate by
Nov 9, 2017
Penalty
Initial $4,889 · Current $0 Reduced
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were run through doorways, windows, floors, or similar openings.    On or about August 3, 2017, and in times prior thereto, an orange extension cord was run through the shop door and into the small mixer area.  The created an electrical hazard to workers in the production area.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4889

1910.334 A02 I

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 26, 2017
Abate by
Nov 9, 2017
Penalty
Initial $4,889 · Current $0 Reduced
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):    On or about August 3, 2017, and in times prior thereto, a SJTY orange extension cord energizing the small mixer had the outer sheath damaged exposing employees to the hazards of electrical shock.  The cord was located next to the maintenance shop.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4889

1904.29 B03

Other-than-serious 1 instance 100 exposed
Issued
Oct 26, 2017
Abate by
Nov 22, 2017
Penalty
Initial $1,000 · Current $0 Reduced
29 CFR 1904.29(b)(3): Each recordable injury or illness was not recorded on the OSHA 300 Log and 301 Incident Report within seven (7) calendar days of receiving information that a recordable injury or illness has occurred.    a) For year(s) 2017, the employer did not record heat related illnesses on the OSHA 300 and 301 forms when workers became ill, were sent home to recover, or were restricted in their work activities for one or more days.
Recent events (2)
  • — I (O) $0
  • — Z (O) $1000

View Ixpalia, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342520160.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.