MILWAUKEE, WI —
OSHA Inspection: ARTISTIC PLATING CO., INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of ARTISTIC PLATING CO., INC. in 405 W. CHERRY ST, MILWAUKEE, WI 53212 (NAICS 332813). OSHA activity number 342523164.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ARTISTIC PLATING CO., INC.
- Site address
- 405 W. CHERRY ST
- City
- MILWAUKEE
- State
- WI
- ZIP
- 53212
- Mailing
- 405 W. CHERRY ST, MILWAUKEE, WI 53212
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332813
- Employees
- 68
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.132 D01
- Issued
- Dec 21, 2017
- Abate by
- Jan 11, 2018
- Penalty
- Initial $3,232 · Current $2,262 Reduced
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards were present, or were likely to be present, which necessitated the use of personal protective equipment: (a) The employer's personal protective equipment (PPE) policy and hazard assessment regarding minimum PPE required to be used by Plating Operators in the Plating Department was deficient, in-that it did not include required use of impermeable aprons to protect Plating Operators from exposure to splashing or dripping of corrosive liquids, such as Nitric Acid used in the passivation tanks in the Gold Room. (b) The employer's personal protective equipment (PPE) policy and hazard assessment regarding minimum PPE required to be used by Plating Operators in the Plating Department was deficient, in-that it did not clearly address required foot wear or use of protective shoe or boot coverings to protect Plating Operators from exposure to splashing or dripping of corrosive liquids, such as Nitric Acid used in the passivation tanks in the Gold Room.
Recent events (2)
- — I (S) $2262.4
- — Z (S) $3232
1910.303 E01 I
- Issued
- Dec 21, 2017
- Abate by
- Jan 19, 2018
- Penalty
- Initial $3,232 · Current $2,262 Reduced
General-duty citation text
29 CFR 1910.303(e)(1)(i): Electric equipment was used without the manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product could be identified. (a) In the Plating Area of the Gold Room, a wall-mounted electrical circuit breaker panelboard with visible corrosion on it was not labeled with the manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product could be identified.
Recent events (2)
- — I (S) $2262.4
- — Z (S) $3232
1910.303 G01 VII
- Issued
- Dec 21, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(vii): Switchboards, panel boards, and distribution boards installed for the control of light and power circuits, and motor control centers were not located in dedicated spaces and protected from damage: a) In the Plating Area of the Gold Room, a wall-mounted electrical circuit breaker panelboard with visible corrosion on it, indicating that it was not adequately protected from damage from corrosive substances.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Dec 21, 2017
- Abate by
- Jan 19, 2018
- Penalty
- Initial $3,232 · Current $2,262 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) On or about August 4, 2017, in the Plating Area of the Gold Room a 25 ft. extension cord, which traversed walkways used by employees, potentially exposed the cord to damage and exposed employees to a tripping hazard. The electrical extension was being used to power a portable electroplating barrel in the "Co Hard Gold Plating Tank" (Tank #01-031).
Recent events (2)
- — I (S) $2262.4
- — Z (S) $3232
More inspections at Artistic Plating CO., INC.
View Artistic Plating CO., INC.'s full OSHA safety record →
More inspections in this industry (NAICS 332813)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342523164.