OSHA Inspection: ARNAN DEVELOPMENT CORPORATION

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of ARNAN DEVELOPMENT CORPORATION in 6459 STATE HIGHWAY 23, ONEONTA, NY 13820 (NAICS 327320). OSHA activity number 342540036.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Arnan Development Corporation — free Get an email when a new federal OSHA severe-injury report for Arnan Development Corporation is published. One employer, no account, unsubscribe in one click.
Site address
6459 STATE HIGHWAY 23
City
ONEONTA
State
NY
ZIP
13820
Mailing
6459 STATE HIGHWAY 23, ONEONTA, NY 13820
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327320
Employees
4
Ownership type
A

6 citations on file for this inspection.

1910.95 G06

Other-than-serious 1 instance 1 exposed
Issued
Nov 14, 2017
Abate by
Dec 18, 2017
Penalty
Initial $4,310 · Current $0 Reduced

Hazardous substances 81108111

29 CFR 1910.95(g)(6): At least annually after obtaining the baseline audiogram, the employer did not obtain a new audiogram for each employee exposed at or above an 8-hour time-weighted average of 85 decibels:      a) Concrete block plant, on or about 8/22/17: An employee engaged in the manufacturing of concrete block was exposed to noise from machinery including, but not limited to, the concrete block machine at a dose of 173.6 % or a noise level of 94.1 decibels (dBA), based on an 8-hour time weighted average (TWA), during the 201 minute sampling period. A zero increment was included for the 279 minutes not sampled. No annual  audiogram was provided within a 12 month period since the last one was on 6/24/16.    Abatement certification must be submitted for tis item.
Recent events (2)
  • — I (O) $0
  • — Z (S) $4310

1910.95 K02

Other-than-serious 1 instance 1 exposed
Issued
Nov 14, 2017
Abate by
Dec 18, 2017
Penalty
Initial $0 · Current $0

Hazardous substances 81108111

29 CFR 1910.95(k)(2): The training program was not repeated annually for each employee included in the hearing conservation program. Information in the training program was not updated to be consistent with changes in protective equipment and work processes:      a) Concrete block plant, on or about 8/22/17:  An employee engaged in the manufacturing of concrete block was exposed to noise from machinery including, but not limited to, the concrete block machine at a dose of 173.6 % or a noise level of   94.1 decibels (dBA), based on an 8-hour time weighted average (TWA), during the 201 minute sampling period. A zero increment was included for the 279 minutes not sampled. The employee was not provided with annual training.    Abatement certification must be submitted for tis item.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.106 E06 I

Serious Gravity 5 1 instance 4 exposed
Issued
Nov 14, 2017
Abate by
Nov 27, 2017
Penalty
Initial $4,310 · Current $3,233 Reduced
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors:    a) Maintenance garage area, on or about 8/22/17: A 20 gallon container of ZEP Brake Flush, a category 2 flammable with a flashpoint of - 18 degrees centigrade, was not electrically grounded to prevent build-up static electricity.    Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $3232.5
  • — Z (S) $4310

1910.106 E06 II

Serious Gravity 5 1 instance 4 exposed
Issued
Nov 14, 2017
Abate by
Nov 27, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(6)(ii): Class I flammable liquid(s) were dispensed into containers without electrically interconnecting the nozzle and the container:   a) Maintenance garage area, on or about 8/22/17: A 20 gallon container of ZEP Brake Flush, a category 2 flammable with a flashpoint of - 18 degrees centigrade, was not electrically interconnected with containers during liquid transfers to prevent build-up static electricity.  Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 H03 III

Serious Gravity 5 1 instance 4 exposed
Issued
Nov 14, 2017
Abate by
Jan 3, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(h)(3)(iii): Employee training did not include the measures employees can take to protect themselves from chemical hazards, including specific procedures the employer had implemented to protect employees from exposure to hazardous chemicals, such as appropriate work practices, emergency procedures and personal protective equipment to be used:   a) Maintenance garage area, on or about 8/22/17: Employees were not trained on measures to protect themselves from the hazard of static electrical discharge during transfers from a 20 gallon container of ZEP Brake Flush, a category 2 flammable with a flashpoint of - 18 degrees centigrade, to smaller pint size containers.  Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C06

Other-than-serious 2 instances 4 exposed
Issued
Nov 14, 2017
Abate by
Jan 31, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirements of this standard are being followed.      a) Concrete block area, on or about 8/21/17: A periodic inspection of equipment with multiple energy sources was not done for equipment in the facility including, but not limited to, the mixer which operates on electrical energy and pneumatic energy, and the cuber which operates on electrical energy and hydraulic energy.     The periodic inspection of lockout/tagout procedures must:   - be performed by an authorized employee other than the ones utilizing the energy control procedure being inspected.     - be conducted to correct any deviations or inadequacies identified.   - include a review, between the inspector and each authorized employee, of that employee's responsibilities under the energy control procedure being inspected.   - include a review between the inspector and each authorized and affected employee, of that employee's responsibilities under the energy control procedure being inspected, and the elements set forth in paragraph (c)(7)(ii) of this section.    Abatement certification must be submitted for this item.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Arnan Development Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342540036.