MIDDLETON, WI ·
OSHA Inspection: HENKELS & MCCOY, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of HENKELS & MCCOY, INC. in 4364 WILLOW LANE RD., MIDDLETON, WI 53562 (NAICS 237130). OSHA activity number 342582590.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HENKELS & MCCOY, INC.
- Site address
- 4364 WILLOW LANE RD.
- City
- MIDDLETON
- State
- WI
- ZIP
- 53562
- Mailing
- 4911 COMMERCE COURT, MC FARLAND, WI 53558
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237130
- Employees
- 100
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
1926.966 G02
- Issued
- Jan 9, 2018
- Abate by
- Jan 24, 2018
- Penalty
- Initial $12,934 · Current $6,467 Reduced
General-duty citation text
29 CFR 1926.966(g)(2): Job briefing. The job briefing required by � 1926.952 shall cover information on special system conditions affecting employee safety, including the location of energized equipment in or adjacent to the work area and the limits of any deenergized work area. On or about August 24, 2017, the pre-job briefing was not specific to the hazards associated with ground removal within the substation, such as temporary grounds were not being used.
Recent events (3)
- · F (O) $6467
- · C (S) $12934
- · Z (S) $12934
1926.962 C
- Issued
- Jan 9, 2018
- Abate by
- Jan 24, 2018
- Penalty
- Initial $12,934 · Current $0 Reduced
General-duty citation text
29 CFR 1926.962(c): Temporary protective grounds were not placed at such locations and arranged in such a manner that the employer can demonstrate will prevent each employee from being exposed to hazardous differences in electric potential: On or about August 24, 2017, temporary protective grounds had not been placed and arranged in such a manner to prevent employee(s) from being exposed to hazardous differences in electrical potential posed by the 138 kV transmission lines running parallel to the de-energized 345 kV transmission lines.
Recent events (3)
- · F (S) $0
- · C (S) $12934
- · Z (S) $12934
More inspections at Henkels & Mccoy, INC.
View Henkels & Mccoy, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 237130)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 342582590.