OSHA Inspection: PSE&G

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of PSE&G in 1036 ANDERSON AVE, FORT LEE, NJ 07024 (NAICS 221122). OSHA activity number 342593746.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pse&G for free Get an email when a new federal OSHA severe-injury report for Pse&G is published. One employer, no account, unsubscribe in one click.
Establishment
PSE&G
Site address
1036 ANDERSON AVE
City
FORT LEE
State
NJ
ZIP
07024
Mailing
325 COUNTY AVENUE, SECAUCUS, NJ 07094
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
6
Ownership type
Private (A)

3 citations on file for this inspection.

1910.269 A04

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Jan 24, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.269(a)(4): Existing characteristics and conditions of electric lines and equipment that were related to the safety of the work to be performed was not determined before work on or near the lines or equipment was started.  Such characteristics and conditions include, but not limited to 1910.269(a)(4)(i) through 1910.269(a)(4)(viii):  (a). Transformer on Utility Pole 0258 FTL - The employer failed to determine that the transformer ground wire was disconnected before work began. An employee received an approximate 7 kV electric shock due to contact with an ungrounded and energized transformer casing while performing secondary line work, on or about 08/24/2017.    There is no abatement certification or documentation required for this item.
Recent events (3)
  • · F (S) $0
  • · C (S) $12934
  • · Z (S) $12934

1910.269 L11

Serious Gravity 10 1 instance 1 exposed
Issued
Jan 24, 2018
Penalty
Initial $0 · Current $12,934
29 CFR 1910.269(l)(11): Non-current-carrying metal parts of equipment or devices, such as transformer cases and circuit-breaker housings, were not treated as energized at the highest voltage to which these parts are exposed, unless the employer inspects the installation and determines that these parts are grounded before employees begin performing the work.    (a). Transformer on Utility Pole 0258 FTL - The employer failed to treat the transformer casing as energized before employees began work. The employer failed to inspect the transformer ground wire to determine whether it was connected before work began. An employee received an approximate 7 kV electric shock due to contact with an ungrounded and energized transformer casing while performing secondary line work, on or about 08/24/2017.      There is no abatement certification or documentation required for this item.
Recent events (3)
  • · F (S) $12934
  • · C (S) $0
  • · Z (S) $0

1910.269 L04 I

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Jan 24, 2018
Abate by
Mar 13, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.269(l)(4)(i): The employer did not ensure that when an employee uses rubber insulating gloves as insulation from energized parts (under paragraph (l)(3)(iii)(A) of this section), the employee shall also use rubber insulating sleeves:  (a). Transformer on Utility Pole 0258 FTL - The employer failed to ensure that employees also use rubber insulating sleeves when using rubber insulating gloves as insulation to energized parts in close proximity. An employee received an approximate 7 kV electric shock to his upper forearm due to contact with an ungrounded and energized transformer casing while performing secondary line work, on or about 08/24/2017.    Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (3)
  • · F (S) $0
  • · C (S) $12934
  • · Z (S) $12934

View Pse&G's full OSHA safety record →