NEPTUNE, NJ —
OSHA Inspection: CANADA DRY BOTTLING COMPANY OF ASBURY PARK
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of CANADA DRY BOTTLING COMPANY OF ASBURY PARK in 437 ROUTE 35 SOUTH, NEPTUNE, NJ 07753 (NAICS 493110). OSHA activity number 342619111.
Where did this inspection happen?
- Establishment
- CANADA DRY BOTTLING COMPANY OF ASBURY PARK
- Site address
- 437 ROUTE 35 SOUTH
- City
- NEPTUNE
- State
- NJ
- ZIP
- 07753
- Mailing
- 437 ROUTE 35 SOUTH, NEPTUNE, NJ 07753
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 49
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.110 E04 III
- Issued
- Penalty
- Initial $5497.00 · Current $3298.00 Reduced
General-duty citation text
29 CFR 1910.110(e)(4)(iii): .LP gas container(s) installed on internal combustion engine vehicles were not securely mounted to prevent jarring loose, slipping or rotating: a) Facility: The LP gas cylinder located on the back side of the Hyster 50 series sit down type (fork lift) power industrial truck was not properly secured. The bracket in the middle of the cylinder was not clipped in during its use as observed on 09/07/2017.
Recent events (2)
- — I (S) $3298
- — Z (S) $5497
1910.303 G01 II
- Issued
- Penalty
- Initial $3298.00 · Current $3298.00
General-duty citation text
29 CFR 1910.303(g)(1)(ii): Working space provided about electrical equipment rated 600 volts, nominal, or less was used for storage:. a) Facility: Electrical panel boxes (voltage 480 Volts/3 phase) were not maintained free of storage material, e.g., boxes of beverage products. A minimum 30 inches of space was not maintained in front of the electrical panels as observed on 9/7/2017.
Recent events (2)
- — I (S) $3298
- — Z (S) $3298
More inspections in this industry (NAICS 493110)
PORTSMOUTH, VA—2026-07-15
DACS INC
WEST CHESTER, OH—2026-07-14
CRESCENT PARK CORPORATION
WEYMOUTH, MA—2026-07-14
SPEEDX
DUNDALK, MD—2026-07-09
WILLIAMS SCOTSMAN, INC.
ROCK HILL, SC—2026-07-08
77566 - WEST MARINE INC
More inspections in NJ
PERTH AMBOY, NJ—2026-07-16
ENGLERT INC.
RIDGEFIELD, NJ—2026-07-16
COLORITE PLASTICS COMPANY
BERLIN, NJ—2026-07-16
URUS CONSTRUCTION CORPORATION
GLASSBORO, NJ—2026-07-15
GLASSBORO WATER & SEWER DEPARTMENT
FLANDERS, NJ—2026-07-15
TRI-STATE QUIKRETE
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342619111.