VICTORIA, TX —
OSHA Inspection: T&D SOLUTIONS, LLC
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of T&D SOLUTIONS, LLC in 1704 DONALSON ROAD, VICTORIA, TX 77901 (NAICS 221119). OSHA activity number 342626512.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- T&D SOLUTIONS, LLC
- Site address
- 1704 DONALSON ROAD
- City
- VICTORIA
- State
- TX
- ZIP
- 77901
- Mailing
- 6411 MASONIC DRIVE P.O. BOX 11948, ALEXANDRIA, LA 71315
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221119
- Employees
- 6
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.67 C02 II
- Issued
- Jan 19, 2018
- Abate by
- Feb 12, 2018
- Penalty
- Initial $12,934 · Current $0 Reduced
General-duty citation text
29 CFR 1910.67(c)(2)(ii): An employee(s) operating an aerial lift(s) was not properly trained: An employee who was not properly trained in aerial lift operations, made direct contact with an energized part, when removing insulated covers while inside the aerial lift bucket; The employee, sustained fatal injuries.
Recent events (3)
- — F (S) $0
- — C (S) $12934
- — Z (S) $12934
1910.269 A02 I A
- Issued
- Jan 19, 2018
- Abate by
- Feb 12, 2018
- Penalty
- Initial $12,934 · Current $12,934
General-duty citation text
29 CFR 1910.269(a)(2)(i)(A): Each employee shall be trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments. Employee was inadequately trained in safety-related work practices pertaining to his job assignment, prior to conducting electrical tasks on a distribution line and sustaining an electrocution.
Recent events (3)
- — F (O) $12934
- — C (S) $12934
- — Z (S) $12934
1910.269 L05 I
- Issued
- Jan 19, 2018
- Abate by
- Feb 12, 2018
- Penalty
- Initial $12,934 · Current $12,934
General-duty citation text
29 CFR 1910.269(l)(5)(i): The employer did not ensure that each employee, to the extent that other safety-related conditions at the worksite permit, works in a position from which a slip or shock will not bring the employee's body into contact with exposed, un-insulated parts energized at a potential different from the employee's. Employee was removing insulated covers from energized parts and was not prevented from working in a position from which a slip or shock would bring the employee's body into contact with the exposed un-insulated energized part.
Recent events (3)
- — F (S) $12934
- — C (S) $12934
- — Z (S) $12934
More inspections at T&D Solutions, LLC
View T&D Solutions, LLC's full OSHA safety record →
More inspections in this industry (NAICS 221119)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342626512.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.