Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NEWELL & HANEY, INC. DBA PRINT MASTER

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of NEWELL & HANEY, INC. DBA PRINT MASTER in 6601 W MAIN ST, BELLEVILLE, IL 62223 (NAICS 323111). OSHA activity number 342630076.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Newell & Haney, INC. DBA Print Master — free Get an email when a new federal OSHA severe-injury report for Newell & Haney, INC. DBA Print Master is published. One employer, no account, unsubscribe in one click.
Site address
6601 W MAIN ST
City
BELLEVILLE
State
IL
ZIP
62223
Mailing
6601 W MAIN ST, BELLEVILLE, IL 62223
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
323111
Employees
9
Ownership type
A

4 citations on file for this inspection.

1910.37 B06

Serious Gravity 5 1 instance 9 exposed
Issued
Oct 3, 2017
Abate by
Nov 21, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  Three exit signs which were not illuminated to a surface value of at least five foot-candles by a reliable light source.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 9 exposed
Issued
Oct 3, 2017
Abate by
Nov 21, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   An electrical power tap was used to supply temporary service to industrial cutting machines such as a paper cutter, which could expose employee to electrical fires.
Recent events (1)
  • — Z (S) $0

1910.305 A02 I

Serious Gravity 5 1 instance 9 exposed
Issued
Oct 3, 2017
Abate by
Nov 21, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installations rated 600 volts, nominal, or less were used for purposes other than those permitted in subparagraphs (A), (B) and (C) of this paragraph:  Employees were exposed to burns due to the use of a temporary electrical power installation which used temporary power for the past 2 years.
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 3, 2017
Abate by
Nov 21, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  Employees were exposed to electrical shocks when the cord of a paper cutting machine did not have strain relief where the cord enters the machine.
Recent events (1)
  • — Z (S) $0

View Newell & Haney, INC. DBA Print Master's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342630076.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.