BELLEVILLE, IL —
OSHA Inspection: NEWELL & HANEY, INC. DBA PRINT MASTER
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of NEWELL & HANEY, INC. DBA PRINT MASTER in 6601 W MAIN ST, BELLEVILLE, IL 62223 (NAICS 323111). OSHA activity number 342630076.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NEWELL & HANEY, INC. DBA PRINT MASTER
- Site address
- 6601 W MAIN ST
- City
- BELLEVILLE
- State
- IL
- ZIP
- 62223
- Mailing
- 6601 W MAIN ST, BELLEVILLE, IL 62223
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323111
- Employees
- 9
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.37 B06
- Issued
- Oct 3, 2017
- Abate by
- Nov 21, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color: Three exit signs which were not illuminated to a surface value of at least five foot-candles by a reliable light source.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Oct 3, 2017
- Abate by
- Nov 21, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: An electrical power tap was used to supply temporary service to industrial cutting machines such as a paper cutter, which could expose employee to electrical fires.
Recent events (1)
- — Z (S) $0
1910.305 A02 I
- Issued
- Oct 3, 2017
- Abate by
- Nov 21, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installations rated 600 volts, nominal, or less were used for purposes other than those permitted in subparagraphs (A), (B) and (C) of this paragraph: Employees were exposed to burns due to the use of a temporary electrical power installation which used temporary power for the past 2 years.
Recent events (1)
- — Z (S) $0
1910.305 G02 III
- Issued
- Oct 3, 2017
- Abate by
- Nov 21, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: Employees were exposed to electrical shocks when the cord of a paper cutting machine did not have strain relief where the cord enters the machine.
Recent events (1)
- — Z (S) $0
More inspections at Newell & Haney, INC. DBA Print Master
View Newell & Haney, INC. DBA Print Master's full OSHA safety record →
More inspections in this industry (NAICS 323111)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342630076.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.