OSHA Inspection: DOMINION ENERGY NUCLEAR CONNECTICUT, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of DOMINION ENERGY NUCLEAR CONNECTICUT, INC. in MILLSTONE POWER STATION ROUTE 156, ROPE FERRY ROAD, WATERFORD, CT 06385 (NAICS 221113). OSHA activity number 342632577.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Dominion Energy Nuclear Connecticut, INC. — free Get an email when a new federal OSHA severe-injury report for Dominion Energy Nuclear Connecticut, INC. is published. One employer, no account, unsubscribe in one click.
Site address
MILLSTONE POWER STATION ROUTE 156, ROPE FERRY ROAD
City
WATERFORD
State
CT
ZIP
06385
Mailing
P.O. BOX 128, WATERFORD, CT 06385
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221113
Employees
1000
Ownership type
A

2 citations on file for this inspection.

1926.1203 A

Deleted Serious Gravity 10 4 instances 10 exposed
Issued
Oct 25, 2017
Abate by
Dec 13, 2017
Penalty
Initial $11,408 · Current $0 Reduced
29 CFR 1926.1203(a): Each employer did not ensure that a competent person identified all confined spaces and identified each space that was a permit space, through consideration and evaluation of the elements of each that space, including testing as necessary:   Jobsite located at the Millstone Power Station, Rope Ferry Road, Waterford, Connecticut:  On, or about, July 3, 2017, the Confined Space Evaluation for each of the following spaces did not account for hazards in each space that had not been eliminated/isolated:  A.  Manhole 21:  Although this confined space was classified as a permit-required confined space due the proximity of the storage and use of inert gases, the potential fire, smoke and shock hazards created by employees performing work in live cable trays and conduits was not considered to be a serious hazard during the evaluation of the space.  B.  Manhole 2:  Although this confined space was classified as a permit-required confined space due the proximity of the storage and use of inert gases, the potential fire, smoke and shock hazards created by employees performing work in live cable trays and conduits was not considered to be a serious hazard during the evaluation of the space.  C.  Manhole 11:  This space was not determined to be a permit-required space although employees were required to perform work in live cable conduits to pull new cables, employees had to touch live cables to enter and exit the space, the floor was wet and the surface conditions were poor due to the presence of an elevated berm, concrete wall and awkward access and egress from the space.  D.  Manhole 32:  This space was not determined to be a permit-required space although employees were required to perform work in live cable conduits to pull new cables, employees had to touch abandoned coils of hanging cable and the floor was wet.
Recent events (3)
  • — F (S) $0
  • — C (S) $11408
  • — Z (S) $11408

1926.1211 C02

Deleted Serious Gravity 5 4 instances 10 exposed
Issued
Oct 25, 2017
Abate by
Dec 13, 2017
Penalty
Initial $6,926 · Current $0 Reduced
29 CFR 1926.1211(c)(2): A mechanical device was not available to retrieve personnel from vertical type permit spaces more than 5 feet (1.52 meters) deep:  Jobsite located at the Millstone Power Station, Rope Ferry Road, Waterford, Connecticut:  On, or about, dates from July 10, 2017 through September 7, 2017, employees entered the following permit required confined spaces for the Open Phase Project.  Mechanical retrieval equipment had not been set-up and staged at the point of entry to be ready for use in the event a rescue from the space was needed:  A.  Manhole 21. B.  Manhole 2. C.  Manhole 11. D.  Manhole 32.
Recent events (3)
  • — F (S) $0
  • — C (S) $6926
  • — Z (S) $6926

View Dominion Energy Nuclear Connecticut, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342632577.