Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: AFP 107 CORP

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of AFP 107 CORP in 40 LODGE ST, ALBANY, NY 12207 (NAICS 721110). OSHA activity number 342680139.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch AFP 107 Corp — free Get an email when a new federal OSHA severe-injury report for AFP 107 Corp is published. One employer, no account, unsubscribe in one click.
Establishment
AFP 107 CORP
Site address
40 LODGE ST
City
ALBANY
State
NY
ZIP
12207
Mailing
40 LODGE ST, ALBANY, NY 12207
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
218
Ownership type
A

10 citations on file for this inspection.

1910.29 B01

Serious Gravity 1 1 instance 8 exposed
Issued
Jan 23, 2018
Abate by
Jan 31, 2018
Penalty
Initial $4,989 · Current $3,000 Reduced
29 CFR 1910.29(b)(1): The top edge height of top rails, or equivalent guardrail system members, were not 42 inches, plus or minus 3 inches, above the walking-working surface:    a) Loading dock, on October 4, 2017, and at times prior, guardrails designed to protect against a 5 foot fall hazard were installed too low to be protective.
Recent events (3)
  • — F (S) $3000
  • — C (S) $4989
  • — Z (S) $4989

1910.141 A03 II

Serious Gravity 1 1 instance 2 exposed
Issued
Jan 23, 2018
Abate by
Apr 30, 2018
Penalty
Initial $4,989 · Current $3,000 Reduced
29 CFR 1910.141(a)(3)(ii): The floor of every workroom was not maintained, so far as practicable, in a dry condition. Where wet processes are used, drainage was not maintained and false floors, platforms, mats, or other dry standing places were not provided.      a) Sump Pump Room, on October 4, 2017, and at times prior, standing water covered a large area of the workroom, and the employer did not provide any means for employees to avoid contact with the standing water.  Employees were exposed to a slip/fall hazard.
Recent events (3)
  • — F (S) $3000
  • — C (S) $4989
  • — Z (S) $4989

1910.303 B08 I

Serious Gravity 1 1 instance 218 exposed
Issued
Jan 23, 2018
Abate by
Feb 6, 2018
Penalty
Initial $4,989 · Current $3,000 Reduced
29 CFR 1910.303(b)(8)(i): Electric equipment was not firmly secured to the surface on which it is mounted.    a) Main Kitchen, on October 4, 2017, and at times prior, an energized receptacle box was not connected to the surface it was placed on, and was hanging by flexible conduit, potentially exposing employees to energized conductors that could become loose.
Recent events (3)
  • — F (S) $3000
  • — C (S) $4989
  • — Z (S) $4989

1910.303 G02 I

Serious Gravity 1 1 instance 2 exposed
Issued
Jan 23, 2018
Abate by
Jan 31, 2018
Penalty
Initial $4,989 · Current $3,000 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:    a) Panelbox in the Electrical Room, "B" Level, on October 4, 2017, and at times prior, the panel cover was removed and conductors were directly connected to circuit breakers in the panel, exposing live parts operating at 120/240 volts.
Recent events (3)
  • — F (S) $3000
  • — C (S) $4989
  • — Z (S) $4989

1910.305 B01 I

Serious Gravity 5 1 instance 218 exposed
Issued
Jan 23, 2018
Abate by
Feb 2, 2018
Penalty
Initial $6,652 · Current $4,500 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed.    a) Kitchen, Room service area, behind the ice machine, on October 4, 2017, and at times prior, a junction box with energized conductors had two unused openings.
Recent events (3)
  • — F (S) $4500
  • — C (S) $6652
  • — Z (S) $6652

1910.305 B02 I

Serious Gravity 5 1 instance 218 exposed
Issued
Jan 23, 2018
Abate by
Jan 31, 2018
Penalty
Initial $8,315 · Current $7,000 Reduced
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings were not provided with covers identified for the purpose.     a) Pool Area, on October 4, 2017, and at times prior, an energized receptacle on the wall near the sump pump room was sticking out of the box exposing live parts and employees to electrocution.
Recent events (3)
  • — F (S) $7000
  • — C (S) $8315
  • — Z (S) $8315

1910.305 J02 I

Serious Gravity 5 2 instances 218 exposed
Issued
Jan 23, 2018
Abate by
Jan 31, 2018
Penalty
Initial $8,315 · Current $7,000 Reduced
29 CFR 1910.305(j)(2)(i): All 15- and 20-ampere attachment plugs and connectors were not constructed so that there are no exposed current-carrying parts except the prongs, blades, or pins:     a) Hot Kitchen area, on October 4, 2017, and at times prior, the outer casing of the cord connector for the Silver Star Food Heater was broken and could expose the inner energized parts.     b) Hot Kitchen Area, on October 4, 2017, and at times prior, the cord for the Walto Show Food Warmer was partially pulled out of the cord connector exposing energized conductors.
Recent events (3)
  • — F (S) $7000
  • — C (S) $8315
  • — Z (S) $8315

1910.159 C10

Other-than-serious 2 instances 218 exposed
Issued
Jan 23, 2018
Penalty
Initial $793 · Current $500 Reduced
29 CFR 1910.159(c)(10): Sprinkler spacing. The employer stored material within the minimum vertical clearance 18 inches (45.7 cm) below the sprinkler head.     a) Kitchen, Dry Food Storage, and Housekeeping Storage area, on October 4, 2017, and at times prior material was stored within the 18 inches (45.7 cm) vertical clearance requirement.
Recent events (3)
  • — F (O) $500
  • — C (O) $793
  • — Z (O) $793

1910.303 F02

Other-than-serious 4 instances 218 exposed
Issued
Jan 23, 2018
Abate by
Feb 2, 2018
Penalty
Initial $933 · Current $600 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    a) Electrical Maintenance Room, Basement Hallway, Sump Pump Room, and Kitchen Dishwashing area(s) on October 4, 2017, and at times prior, the circuit breaker panels in these areas did not have each circuit breaker labeled to indicate its purpose.
Recent events (3)
  • — F (O) $600
  • — C (O) $933
  • — Z (O) $933

1910.303 G01

Other-than-serious 15 instances 218 exposed
Issued
Jan 23, 2018
Penalty
Initial $793 · Current $500 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:     a) All Electrical Panels observed in the basement hallway, housekeeping storage, and kitchen areas, on October 4, 2017, and at times prior, the required working space in front and sides of electrical panel boxes was blocked.
Recent events (3)
  • — F (O) $500
  • — C (O) $793
  • — Z (O) $793

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342680139.