WEBSTER, NY —
OSHA Inspection: STUDCO BUILDING SYSTEMS US LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of STUDCO BUILDING SYSTEMS US LLC in 1700 BOULTER INDUSTRIAL PARK, WEBSTER, NY 14580 (NAICS 444190). OSHA activity number 342696796.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- STUDCO BUILDING SYSTEMS US LLC
- Site address
- 1700 BOULTER INDUSTRIAL PARK
- City
- WEBSTER
- State
- NY
- ZIP
- 14580
- Mailing
- 1700 BOULTER INDUSTRIAL PARK, WEBSTER, NY 14580
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 444190
- Employees
- 45
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.23 B10
- Issued
- Nov 2, 2017
- Abate by
- Feb 5, 2018
- Penalty
- Initial $5,070 · Current $3,667 Reduced
General-duty citation text
29 CFR 1910.23(b)(10): The employer did not ensure that any ladder with structural or other defects was immediately tagged "Dangerous: Do Not Use" or with similar language in accordance with �1910.145 and removed from service until repaired in accordance with �1910.22(d), or replaced; a) On or about 10/11/17 in the storage area; On or about 10/11/17 in the storage area; employees were exposed to fall hazards when the eight step mobile ladder had two bent lower brackets causing one of the rear wheels to raise and not contact the ground resulting in ladder instability. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $3667
- — Z (S) $5070
1910.30 B01
- Issued
- Nov 2, 2017
- Abate by
- Feb 5, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.30(b)(1): The employer did not train each employee on or before May 17, 2017 in the proper care, inspection, storage, and use of equipment covered by this subpart before an employee used the equipment. a) On or about 10/11/17 in the storage area; On or about 10/11/17 in the storage area; employees were exposed to fall hazards when the employer did not provide employee training on the need to inspect equipment such as but not limited to, the eight step mobile ladder (that had two bent lower brackets causing one of the rear wheels to raise and not contact the ground resulting in ladder instability) prior to use and to tag it out of service. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.28 B01 I
- Issued
- Nov 2, 2017
- Abate by
- May 7, 2018
- Penalty
- Initial $5,070 · Current $3,667 Reduced
General-duty citation text
29 CFR 1910.28(b)(1)(i): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that was 4 feet (1.2 m) or more above a lower level was protected from falling by one or more of the following: Guardrail systems, safety net systems, or personal fall arrest systems: a) On or about 10/11/17 in the Incoming Truck Bay; employees remove strapping, hold downs, position and guide coils of steel weighing between 500 - 6,000 lbs. from delivery trucks using an overhead crane and were exposed to an five feet fall from the unprotected edge of the truck bed to the lower level, i.e. surface of the truck bay. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $3667
- — Z (S) $5070
1910.30 A01
- Issued
- Nov 2, 2017
- Abate by
- Feb 5, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.30(a)(1): Employer did not ensure on or before May 17, 2017 training on the use of a fall protection system before they were exposed to a fall hazard. a) On or about 10/11/17 in the Incoming Truck Bay; employees remove strapping, hold downs, position and guide coils of steel weighing between 500 - 6,000 lbs. from delivery trucks using an overhead crane and were exposed to an five feet fall from the unprotected edge of the truck bed to the lower level, i.e. surface of the truck bay, when the employer did not provide training on the use of a fall protection system. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.176 A
- Issued
- Nov 2, 2017
- Abate by
- Feb 5, 2018
- Penalty
- Initial $5,070 · Current $3,666 Reduced
General-duty citation text
29 CFR 1910.176(a): Aisle(s) and passageway(s) were not kept clear and in good repair with no obstruction across or in aisles that could create a hazard. a) On or about 10/11/17 in coil storage area; employees were exposed to trip and fall hazards while moving unloading coils weighing between 2,200 - 4,500 lbs. from a delivery truck when the main aisle, running north and south, was being used as a staging area and blocked with stacked of coils. b) On or about 10/11/17 in the coil storage area; employees were exposed to trip and fall hazards while locating and moving metal coils, weighing between 2,200 lbs. - 4,500 lbs. using the overhead crane, when the west row between rows 2 & 3 was blocked with coils. c) On or about 10/11/17 in the coil storage area; employees were exposed to trip and fall hazards while locating and moving coils, weighing between 2,200 - 4,500 lbs. using an overhead crane, when west row between rows 4 & 5 were blocked with coils. d) On or about 10/11/17 in the coil storage area; employees were exposed to trip and fall hazards while locating and moving coils, weighing between 2,200 - 4,500 lbs. using an overhead crane, when west row between rows 12 & 13 were blocked with coils. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $3666
- — Z (S) $5070
1910.176 B
- Issued
- Nov 2, 2017
- Abate by
- Feb 5, 2018
- Penalty
- Initial $6,338 · Current $0 Reduced
General-duty citation text
29 CFR 1910.176(b): Storage of material created a hazard: a) On or about 10/11/17 in coil storage area; a row of coils, some as high as 10 feet, were stacked to the north of row #1, effectively blocking access to these coils necessitating employees to climb a stack of coils, some as high as 10 feet in row #1, to insert the coil lifting device when removal of these coils was required. b) On or about 10/11/17 in the coil storage area; a row of coils, some as high as 10 feet, were stacked to the south of row #16, effectively blocking access to these coils necessitating employees to climb a stack of coils, some as high as 10 feet, in row #16 to insert the coil lifting device when removal of these coils was required. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $6338
1910.303 B08 I
- Issued
- Nov 2, 2017
- Abate by
- Feb 5, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(8)(i): Electrical equipment was not firmly secured to the surface on which it was mounted: a) On or about 10/11/17 in the Dispatch workbench area; employees were exposed to contact with electrical current when an metal receptacle box with knockouts was suspended by an unsupported rigid conduit above a stack of wooden banding material. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 444190)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342696796.