OSHA Inspection: LAUNDRY WAVE INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of LAUNDRY WAVE INC in 500 LEXINGTON AVE., CLIFTON, NJ 07011 (NAICS 236220). OSHA activity number 342707544.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Laundry Wave INC for free Get an email when a new federal OSHA severe-injury report for Laundry Wave INC is published. One employer, no account, unsubscribe in one click.
Establishment
LAUNDRY WAVE INC
Site address
500 LEXINGTON AVE.
City
CLIFTON
State
NJ
ZIP
07011
Mailing
500 LEXINGTON AVE, CLIFTON, NJ 07011
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
3
Ownership type
Private (A)

3 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 2 instances 2 exposed
Issued
Apr 6, 2018
Penalty
Initial $2,217 · Current $1,330 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:   a) Laundry Room: Employees engaged in trim work were exposed to electric shock while connecting electric tools to metal boxes fed by BX cables, on or about 10/16/17.  b) Laundry Room: Employees engaged in tile work were exposed to electric shock while operating an electric saw controlled  by a single pole switch mounted on a plastic box, on or about 10/31/17
Recent events (2)
  • · I (S) $1330.2
  • · Z (S) $2217

1926.405 A02 II B

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 6, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.405(a)(2)(ii)(B): Runs of open conductors used as temporary wiring branch circuits were located where the conductors would be subject to physical damage, or the conductors were fastened at intervals exceeding 10 feet:    a) Laundry Room: Employees were exposed to electric shock while working around a live electric branch circuits that were laying on the floor and not protected against damage, on or about 10/16/17.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1926.403 I02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 6, 2018
Penalty
Initial $2,772 · Current $1,663 Reduced
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph.  a) Utility Room: Employees were exposed to electric shock while working around a live electric panel that was protected with a piece of cardboard, on or about 10/16/17.