On , OSHA opened a complaint safety inspection of HENBERT INTERIORS FINISHING INC in 87-76 130TH STREET, RICHMOND HILL, NY 11418 (NAICS 337212). OSHA activity number 342725652.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HENBERT INTERIORS FINISHING INC
- Site address
- 87-76 130TH STREET
- City
- RICHMOND HILL
- State
- NY
- ZIP
- 11418
- Mailing
- 87-76 130TH STREET, RICHMOND HILL, NY 11418
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 337212
- Employees
- 12
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.36 D01
- Issued
- Apr 18, 2018
- Penalty
- Initial $3,696 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge. (a) On or about October 19, 2017, at 87-16 130th Street, Richmond Hill, NY 11418 Employees preforming work duties in workshop in which emergency exit was locked with roll down gate. ABATEMENT CERTIFICATION NOT REQUIRED PURSUANT TO 29 CFR 1903.19
Recent events (2)
- — I (S) $2500
- — Z (S) $3696
1910.303 B07 I
- Issued
- Apr 18, 2018
- Abate by
- Apr 30, 2018
- Penalty
- Initial $3,696 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment. (a) On or about October 24, 2017, at 87-16 130th Street, Richmond Hill, NY 11418 An electrical box marked "vaccun" (next to box marked "green vacuum no. 3) located on the wall adjacent to the dust collectors had an uncovered hole, allowing combustible wood dust to infiltrate and accumulate inside the box, as well as potentially allowed contact with or damage to live wires. (b) On or about October 24, 2017, at 87-16 130th Street, Richmond Hill, NY 11418 A four outlet electrical box located on the wall near the dust collectors had an uncovered hole, allowing combustible wood dust to infiltrate and accumulate inside the box, as well as potentially allowed contact with or damage to live wires. (c) On or about October 24, 2017, at 87-16 130th Street, Richmond Hill, NY 11418 An electrical box attached behind a switch box marked "light" and "heat" and located on the wall adjacent to the dust collectors had an uncovered hole, allowing combustible wood dust to infiltrate and accumulate inside the box, as well as potentially allowed contact with or damage to live wires. ABATEMENT CERTIFICATION REQUIRED PURSUANT TO 29 CFR 1903.19
Recent events (2)
- — I (S) $2500
- — Z (S) $3696
1910.303 G02 I
- Issued
- Apr 18, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): (a) On or about April 2, 2018 at 87-16 130th Street, Richmond Hill, NY 11418 Employees preforming work duties in workshop where face plates missing on light switches are exposing them to live parts. ABATEMENT CERTIFICATION REQUIRED PURSUANT TO 29 CFR 1903.19
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 B02 II
- Issued
- Apr 18, 2018
- Abate by
- Jun 1, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(2)(ii): Receptacles having grounding contacts did not have contacts that were effectively grounded. (a) On or about October 24, 2017, at 87-16 130th Street, Richmond Hill, NY 11418 A four outlet electrical box located on the wall near the dust collectors had a receptacle which was not properly grounded. ABATEMENT CERTIFICATION REQUIRED PURSUANT TO 29 CFR 1903.19
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 A02 X
- Issued
- Apr 18, 2018
- Abate by
- Apr 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage. (a) On or about October 24, 2017, at 87-16 130th Street, Richmond Hill, NY 11418 A yellow flexible cord which was hardwired to connect a switch box to the Grizzly Industrial Model G1030Z2 dust collector (serial number M065131) had multiple cuts on its outer insulation, exposing the wires underneath to further damage. ABATEMENT CERTIFICATION REQUIRED PURSUANT TO 29 CFR 1903.19
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV
- Issued
- Apr 18, 2018
- Abate by
- May 14, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv): Extension cords and/or power strips were being used in lieu of permanent building wiring. (a) On or about April 2, 2018, at 87-16 130th Street, Richmond Hill, NY 11418 Employees working in office where temporary wiring is being used to power a coffee pot, a microwave and a refrigerator. ABATEMENT CERTIFICATION REQUIRED PURSUANT TO 29 CFR 1903.19
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.157 C01
- Issued
- Apr 18, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: (a) On or about April 2, 2018 at 87-16 130th Street, Richmond Hill, NY 11418 Employees worked in workshop where fire extinguishers were not properly identified. ABATEMENT CERTIFICATION REQUIRED PURSUANT TO 29 CFR 1903.19
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Henbert Interiors Finishing INC
View Henbert Interiors Finishing INC's full OSHA safety record →
More inspections in this industry (NAICS 337212)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342725652.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.