Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. GENERAL SERVICES ADMINISTRATION

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of U.S. GENERAL SERVICES ADMINISTRATION in 315 W. ALLEGAN ST, LANSING, MI 48933 (NAICS 921190). OSHA activity number 342736626.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. General Services Administration — free Get an email when a new federal OSHA severe-injury report for U.S. General Services Administration is published. One employer, no account, unsubscribe in one click.
Site address
315 W. ALLEGAN ST
City
LANSING
State
MI
ZIP
48933
Mailing
110 MICHIGAN ST. N.W. RM. 293, GRAND RAPIDS, MI 49503
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
Yes
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
921190
Employees
1
Ownership type
D

8 citations on file for this inspection.

1910.1025 H01

Serious Gravity 10 14 instances 2 exposed
Issued
Mar 23, 2018
Abate by
May 4, 2018
Penalty
Initial $0 · Current $0

Hazardous substances 1591

29 CFR 1910.1025(h)(1): All surfaces were not maintained as free as practicable of accumulations of lead:  On or about September 28, 2017 and at times thereafter, the employer did not ensure all employees were protected from lead surface contamination. Lead was identified in/on: air handling units, air filters associated with air handling units, light switches, floors/floor mats, doors, HVAC vents and shelving units.
Recent events (3)
  • — W (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.1027 K01

Serious Gravity 5 5 instances 2 exposed
Issued
Mar 23, 2018
Abate by
May 4, 2018
Penalty
Initial $0 · Current $0

Hazardous substances C141

29 CFR 1910.1027(k)(1): Surfaces were not maintained as free as practicable of accumulations of cadmium:  On or about September 28, 2017 and at times thereafter, the employer did not ensure all employees were protected from cadmium surface contamination. Cadmium was identified in/on air handling units.
Recent events (3)
  • — W (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.1200 E01

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 23, 2018
Abate by
Apr 13, 2018
Penalty
Initial $0 · Current $0

Hazardous substances 026015919020C141

29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:  On or about October 30, 2017, the employer did not develop and implement the elements of a hazard communication program. The program failed to include methods to inform other employers of any precautionary measures that need to be taken to protect all employees exposed to hazardous chemicals such as, but not limited to, heavy metals and asbestos which are present in various building materials.
Recent events (3)
  • — W (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.1025 M01 III

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 23, 2018
Abate by
Apr 13, 2018
Penalty
Initial $0 · Current $0

Hazardous substances 1591

29 CFR 1910.1025(m)(1)(iii): Employers shall include lead in the hazard communication program established to comply with the HCS (� 1910.1200). Employers shall ensure that each employee has access to labels on containers of lead and to safety data sheets, and is trained in accordance with the requirements of HCS and paragraph (l) of this section.  On or about October 30, 2017, the employer did not ensure lead was included in the hazard communication program for all employees conducting work in the Chamberlain Federal Building.
Recent events (3)
  • — W (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.1025 L01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 23, 2018
Abate by
Apr 13, 2018
Penalty
Initial $0 · Current $0

Hazardous substances 1591

29 CFR 1910.1025(l)(1)(i): Employee(s) working in an area where there is potential exposure to airborne lead at any level were not informed of the content of Appendices A and B of 29 CFR 1910.1025:  On or about December 6, 2017, the employer did not inform all employees who work in locations with potential exposure to airborne lead such as inside air handling units of the contents of Appendices A and B of 29 CFR 1910.1025.
Recent events (3)
  • — W (S) $0
  • — C (S) $0
  • — Z (S) $0

1926.1101 K01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 23, 2018
Abate by
Apr 13, 2018
Penalty
Initial $0 · Current $0

Hazardous substances 9020

29 CFR 1926.1101(k)(1)(ii): Employers shall include asbestos in the hazard communication program established to comply with the HCS (� 1910.1200). Employers shall ensure that each employee has access to safety data sheets.   On or about October 30, 2017, the employer did not ensure asbestos was included in the hazard communication program for all employees conducting work in the Chamberlain Federal Building.
Recent events (3)
  • — W (S) $0
  • — C (S) $0
  • — Z (S) $0

1960.34 A06

Repeat Gravity 5 1 instance 2 exposed
Issued
Mar 23, 2018
Abate by
May 4, 2018
Penalty
Initial $0 · Current $0

Hazardous substances 02601591C141

29 CFR 1960.34(a)(6): The Administrator or the Administrator's designee did not abate unsafe or unhealthful conditions disclosed by reports, investigation or inspections within 30 calendar days or submit to the occupant agency's designated liaison official an abatement plan.  On or about December 18, 2017, the General Services Administration was made aware of lead, arsenic and cadmium contamination in the air handling units in the Chamberlain Federal Building and did not abate the unhealthful conditions within 30 calendar days or submit an abatement plan to the occupant agency's officials.    General Services Administration was previously cited for a violation of this Occupational Safety and Health Standard 29 CFR 1960.34(a)(6), which was contained in OSHA inspection number 958784, notice number 1, item number 1 and was affirmed as a final order on July 3, 2014, with respect to a workplace located at U.S. Customs House, Room 222, 200 Chestnut Street, Philadelphia, PA 19106.
Recent events (3)
  • — W (R) $0
  • — C (R) $0
  • — Z (R) $0

1910.1025 D02

Other-than-serious 2 instances 1 exposed
Issued
Mar 23, 2018
Abate by
Apr 13, 2018
Penalty
Initial $0 · Current $0

Hazardous substances 1591

29 CFR 1910.1025(d)(2): An initial determination was not made to determine if any employee may be exposed to lead at or above the action level:  a) On or about October 30, 2017, the employer did not determine if any employees were exposed to lead at or above the action level when performing tasks such as filter changes and routine cleaning activities.  b) On or about October 4, 2017, the employer did not determine if any employees were exposed to lead at or above the action level after a release of dust and debris containing lead occurred during the removal of an air handling unit and associated duct work.
Recent events (3)
  • — W (O) $0
  • — C (O) $0
  • — Z (O) $0

View U.S. General Services Administration's full OSHA safety record →