Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: AZTEC INDUSTRIES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of AZTEC INDUSTRIES, INC. in 14621 MARINE RD., HUMBLE, TX 77396 (NAICS 332312). OSHA activity number 342749306.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Aztec Industries, INC. — free Get an email when a new federal OSHA severe-injury report for Aztec Industries, INC. is published. One employer, no account, unsubscribe in one click.
Site address
14621 MARINE RD.
City
HUMBLE
State
TX
ZIP
77396
Mailing
14621 MARINE RD., HUMBLE, TX 77396
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332312
Employees
15
Ownership type
A

8 citations on file for this inspection.

1910.253 B04 III

Serious Gravity 5 1 instance 15 exposed
Issued
Feb 6, 2018
Abate by
Apr 6, 2018
Penalty
Initial $3,696 · Current $2,000 Reduced
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least 1 half hour.      On or about November 2, 2017 at the facility where employees were exposed to a fire hazard when acetylene cylinders were stored with oxygen cylinders without being separated by a minimum distance of 20 feet or by a noncombustible barrier at least 5 feet high with a 1 hour fire rating.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $3696

1910.303 F02

Serious Gravity 5 2 instances 15 exposed
Issued
Feb 6, 2018
Abate by
Mar 2, 2018
Penalty
Initial $3,696 · Current $2,000 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:      On or about November 2, 2017 at the fabrication shop where two breaker boxes were not labeled to identify each breaker and or switch.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $3696

1910.305 B01 II

Serious Gravity 5 5 instances 15 exposed
Issued
Feb 6, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    a. On or about November 2, 2017 at the fabrication shop, where employees were exposed to electrical hazards when accessing an Eaton breaker box which had missing breakers or blanks.     b. On or about November 2, 2017 at the fabrication shop, where employees were exposed to electrical hazards when working near a disconnect box which was missing a knock out.     c. On or about November 2, 2017 at the fabrication shop, where employees were exposed to electrical hazards when accessing a GE breaker box which had missing breakers or blanks and a missing knock out.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 4 instances 15 exposed
Issued
Feb 6, 2018
Penalty
Initial $3,696 · Current $2,000 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):     On or about November 2, 2017 at the fabrication shop where employees were exposed to electrical hazards when using electrical wall outlets, a light switch, and a breaker box where the cover was missing or broken.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $3696

1910.305 G02 III

Serious Gravity 5 1 instance 15 exposed
Issued
Feb 6, 2018
Abate by
Mar 2, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:    On or about November 2, 2017 at the fabrication shop where employees were exposed to electrical hazards when using welding machines whose power cables were connected to the breaker box without having strain relief.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 E01

Serious Gravity 5 1 instance 15 exposed
Issued
Feb 6, 2018
Abate by
Apr 6, 2018
Penalty
Initial $3,696 · Current $2,000 Reduced
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:      On or about November 2, 2017, where employees were using compressed gases such as, but not limited to, acetylene, propylene, argon, and diesel fuel without a written hazard communication program in place.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $3696

1910.1200 H01

Serious Gravity 5 1 instance 15 exposed
Issued
Feb 6, 2018
Abate by
Apr 6, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area:      On or about November 2, 2017, where employees were using compressed gases such as, but not limited to, acetylene, propylene, argon, and diesel fuel and had not been trained on the hazards of the chemicals they use.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 G01

Serious Gravity 5 1 instance 15 exposed
Issued
Feb 6, 2018
Abate by
Apr 6, 2018
Penalty
Initial $3,696 · Current $2,000 Reduced
29 CFR 1910.1200(g)(1): Employers did not have a safety data sheet in the workplace for each hazardous chemical which they use.      On or about November 2, 2017, where employees worked with compressed gases such as, but not limited to, acetylene, propylene, argon, and diesel fuel without the employer having safety data sheets available.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $3696