Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NEW RIVER ELECTRICAL CORPORATION

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of NEW RIVER ELECTRICAL CORPORATION in 3887 MARSHA DRIVE, COLUMBUS, OH 43207 (NAICS 238210). OSHA activity number 342770062.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch NEW River Electrical Corporation — free Get an email when a new federal OSHA severe-injury report for NEW River Electrical Corporation is published. One employer, no account, unsubscribe in one click.
Site address
3887 MARSHA DRIVE
City
COLUMBUS
State
OH
ZIP
43207
Mailing
15 CLOVERDALE PLACE, CLOVERDALE, VA 24077
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
1000
Ownership type
A

3 citations on file for this inspection.

1926.961 B04 II

Serious Gravity 10 1 instance 200 exposed
Issued
Feb 22, 2018
Abate by
Sep 14, 2022
Penalty
Initial $12,934 · Current $12,934
29 CFR 1926.961(b)(4)(ii): Each crew shall independently comply with this section and, if there is no system operator in charge of the lines or equipment, shall have separate tags and coordinate deenergizing and reenergizing the lines and equipment with the other crews.   a. On or before November 6, 2017 where employees were preparing an electrical cable for the installation of a pothead, the riser crew and the underground residential distribution crew did not independently ground and tag the cables when deenergizing and reenergizing the system, resulting in the hospitalization of an employee due to the resulting shock.
Recent events (3)
  • — J (S) $12934
  • — C (S) $12934
  • — Z (S) $12934

1926.961 C02

Deleted Serious Gravity 10 1 instance 200 exposed
Issued
Feb 22, 2018
Abate by
Mar 14, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1926.961(c)(2): Open disconnecting means. The employer shall ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized are open. The employer shall render such means inoperable, unless its design does not so permit, and then ensure that such means are tagged to indicate that employees are at work.  a. On or before November 6, 2017 where employees were preparing an electrical cable for the installation of a pothead, the disconnecting means in the loop were not open, had not been made inoperable, and were not tagged, which resulted in serious injuries and hospitalization of an employee from electrical shock .
Recent events (3)
  • — J (S) $0
  • — C (S) $12934
  • — Z (S) $12934

1926.962 B

Deleted Serious Gravity 10 1 instance 200 exposed
Issued
Feb 22, 2018
Abate by
Mar 14, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1926.962(b): General. For any employee to work transmission and distribution lines or equipment as deenergized, the employer shall ensure that the lines or equipment are deenergized under the provisions of � 1926.961 and shall ensure proper grounding of the lines or equipment as specified in paragraphs (c) through (h) of this section. However, if the employer can demonstrate that installation of a ground is impracticable or that the conditions resulting from the installation of a ground would present greater hazards to employees than working without grounds, the lines and equipment may be treated as deenergized provided that the employer establishes that all of the following conditions apply:  a. On or before November 6, 2017 where employees were preparing electrical cables for the installation of potheads, the ends of the cables were not grounded at the transformer, resulting in the connection of the cable at the transformer, resulting in the hospitalization of an employee as a result of the electrical shock.