PECOS, TX —
OSHA Inspection: PACESETTER DRILLING, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of PACESETTER DRILLING, LLC in 15.9 MILES SOUTHEAST FROM PECOS, TX, PECOS, TX 79772 (NAICS 213111). OSHA activity number 342784360.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PACESETTER DRILLING, LLC
- Site address
- 15.9 MILES SOUTHEAST FROM PECOS, TX
- City
- PECOS
- State
- TX
- ZIP
- 79772
- Mailing
- 12505 W. CR 125, ODESSA, TX 79764
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 213111
- Employees
- 72
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.304 G05
- Issued
- Mar 6, 2018
- Abate by
- Mar 23, 2018
- Penalty
- Initial $3,628 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: On or about November 15, 2017, the trip tank was not grounded; the ground rod was on the ground lying against the tank. This exposed employees to electric shock and/or burn hazards.
Recent events (2)
- — I (O) $3000
- — Z (S) $3628
1910.157 C04
- Issued
- Mar 6, 2018
- Abate by
- Mar 23, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(4): Portable fire extinguishers were not maintained in a fully charged and operable condition: On or about November 15, 2017, the fire extinguisher on the mud pit near the shakers was not operational. This exposed employees to fire hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 A02 X
- Issued
- Mar 6, 2018
- Abate by
- Mar 23, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(x): 29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points: On or about November 15, 2017, the engine room had four 120v cables running through a hole on the metal wall which had very jagged edges. This exposed employees to shock hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Pacesetter Drilling, LLC
View Pacesetter Drilling, LLC's full OSHA safety record →
More inspections in this industry (NAICS 213111)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342784360.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.