BUFFALO, NY —
OSHA Inspection: PVS CHEMICAL SOLUTIONS, INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of PVS CHEMICAL SOLUTIONS, INC. in 55 LEE STREET, BUFFALO, NY 14210 (NAICS 325188). OSHA activity number 342798337.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PVS CHEMICAL SOLUTIONS, INC.
- Site address
- 55 LEE STREET
- City
- BUFFALO
- State
- NY
- ZIP
- 14210
- Mailing
- 55 LEE STREET, BUFFALO, NY 14210
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325188
- Employees
- 47
- Ownership type
- A
Citations
1 citation on file for this inspection.
1910.111 B09 IX
- Issued
- Jun 5, 2018
- Abate by
- Jul 6, 2018
- Penalty
- Initial $7,853 · Current $0 Reduced
General-duty citation text
29 CFR 1910.111(b)(9)(ix): A hydrostatic relief valve was not installed between each pair of valves in the liquid ammonia piping or hose where liquid could be trapped so as to relieve into the atmosphere at a safe location: a) Ammonium thiosulfate building - On or about 3/21/2018, the five Rego hydrostatic relief valves (one at the top of the Gassing tank, two at the top of Digest tank #1, and two at the top of Digest tank #2) have been installed in the anhydrous ammonia pipeline and release inside the building. ABATEMENT CERTIFICATION REQUIRED.
Recent events (3)
- — J (O) $0
- — C (S) $7853
- — Z (S) $7853
More inspections at PVS Chemical Solutions, INC.