Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CITIZENS ELECTRIC CORPORATION

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CITIZENS ELECTRIC CORPORATION in ROCKY RIDGE SUBSTATION, STE GENEVIEVE, MO 63670 (NAICS 221121). OSHA activity number 342814738.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Citizens Electric Corporation — free Get an email when a new federal OSHA severe-injury report for Citizens Electric Corporation is published. One employer, no account, unsubscribe in one click.
Site address
ROCKY RIDGE SUBSTATION
City
STE GENEVIEVE
State
MO
ZIP
63670
Mailing
PO BOX 368, PERRYVILLE, MO 63775
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221121
Employees
85
Ownership type
A

3 citations on file for this inspection.

1910.269 M03 II

Serious Gravity 10 1 instance 3 exposed
Issued
Mar 16, 2018
Abate by
Apr 11, 2018
Penalty
Initial $9,054 · Current $9,054
29 CFR 1910.269(m)(3)(ii): The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be denenergized were open.  The employer did not render such means inoperable, unless its design does not so permit, and then sure that such means are tagged to indicate that employees are at work:    On 12/1/2017, three employees were changing out "A" phase regulator and did not ensure the bypass, source, and load switches had been positioned to de-energize it. A ground connection was removed while the regulator was energized and an employee received a serious electric shock.
Recent events (2)
  • — I (S) $9054
  • — Z (S) $9054

1910.269 M03 VI

Serious Gravity 10 1 instance 3 exposed
Issued
Mar 16, 2018
Abate by
Apr 11, 2018
Penalty
Initial $9,054 · Current $0 Reduced
29 CFR 1910.269(m)(3)(vi): 29 CFR 1910.269(m)(3)(vi): After the applicable requirements in paragraphs (m)(3)(i) through (m)(3)(v) of this section have been followed and the system operator gives a clearance to the employee in charge, the employer did not ensure that the lines and equipment are deenergized by testing the lines and equipment to be worked with a device designed to detect voltage:    At the time of the electric shock on 12/1/2017, the "A" single phase regulator was not tested to verify the hazard was removed. An employee received a serious electric shock when he removed a ground connection while the regulator was energized.
Recent events (2)
  • — I (S) $0
  • — Z (S) $9054

1910.269 C02

Other-than-serious 1 instance 3 exposed
Issued
Mar 16, 2018
Abate by
Apr 11, 2018
Penalty
Initial $9,054 · Current $6,338 Reduced
29 CFR 1910.269(c)(2): The job briefing did not cover at least the following subjects:  hazards associated with the job, work procedures involved, special precautions, energy-source controls, and personal protective equipment requirements:    The job briefing on 12/1/2017 did not adequately cover energy-source controls. The briefing did not cover testing for voltage before working on removing "A" phase regulator. The briefing did not cover the need to remove the ground cable last to prevent removing the ground protection it provided.
Recent events (2)
  • — I (O) $6337.8
  • — Z (S) $9054

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342814738.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.