Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MIDWOOD DISTRIBUTORS INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of MIDWOOD DISTRIBUTORS INC in SUGARMANS PLAZA 600 SCRANTON CARBONDALE HWY, EYNON, PA 18403 (NAICS 493110). OSHA activity number 342850443.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Midwood Distributors INC — free Get an email when a new federal OSHA severe-injury report for Midwood Distributors INC is published. One employer, no account, unsubscribe in one click.
Site address
SUGARMANS PLAZA 600 SCRANTON CARBONDALE HWY
City
EYNON
State
PA
ZIP
18403
Mailing
120 JERSEY AVENUE, NEW BRUNSWICK, NJ 08901
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
10
Ownership type
A

2 citations on file for this inspection.

1910.303 F02

Serious Gravity 5 1 instance 10 exposed
Issued
Jan 10, 2018
Abate by
Jan 31, 2018
Penalty
Initial $2,956 · Current $2,069 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident.  a) South Wall, Electrical Room, Warehouse, 600 Scranton-Carbondale Highway, Eynon, PA - Four (4) Westinghouse FDP365 - 400A, 600V Hardware Overcurrent Switch Units and two (2) Westinghouse FDPT3633 - 100A, 600V Panelboard Overcurrent Switch Units were not marked to indicate their purpose exposing employees to electrical hazards in the event of an electrical incident, as observed on or about December 21, 2017.  In accordance with 29 CFR 1903.19, abatement certification is required for this violation.
Recent events (2)
  • — I (S) $2069.2
  • — Z (S) $2956

1910.304 F01 VIII

Serious Gravity 5 1 instance 10 exposed
Issued
Jan 10, 2018
Abate by
Jan 31, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD."  a) South Wall, Electrical Room, Warehouse, 600 Scranton-Carbondale Highway, Eynon, PA - A Westinghouse FDP365 - 400A, 600V Hardware Overcurrent Switch Unit not listed or marked "SWD" was used by employees on a daily basis to operate the warehouse lighting circuit (277-volt fluorescent lights) exposing the employees to the hazards of an arc flash, as observed on or about December 21, 2017.  In accordance with 29 CFR 1903.19, abatement certification is required for this violation.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342850443.