EYNON, PA —
OSHA Inspection: MIDWOOD DISTRIBUTORS INC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of MIDWOOD DISTRIBUTORS INC in SUGARMANS PLAZA 600 SCRANTON CARBONDALE HWY, EYNON, PA 18403 (NAICS 493110). OSHA activity number 342850443.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MIDWOOD DISTRIBUTORS INC
- Site address
- SUGARMANS PLAZA 600 SCRANTON CARBONDALE HWY
- City
- EYNON
- State
- PA
- ZIP
- 18403
- Mailing
- 120 JERSEY AVENUE, NEW BRUNSWICK, NJ 08901
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 10
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.303 F02
- Issued
- Jan 10, 2018
- Abate by
- Jan 31, 2018
- Penalty
- Initial $2,956 · Current $2,069 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident. a) South Wall, Electrical Room, Warehouse, 600 Scranton-Carbondale Highway, Eynon, PA - Four (4) Westinghouse FDP365 - 400A, 600V Hardware Overcurrent Switch Units and two (2) Westinghouse FDPT3633 - 100A, 600V Panelboard Overcurrent Switch Units were not marked to indicate their purpose exposing employees to electrical hazards in the event of an electrical incident, as observed on or about December 21, 2017. In accordance with 29 CFR 1903.19, abatement certification is required for this violation.
Recent events (2)
- — I (S) $2069.2
- — Z (S) $2956
1910.304 F01 VIII
- Issued
- Jan 10, 2018
- Abate by
- Jan 31, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." a) South Wall, Electrical Room, Warehouse, 600 Scranton-Carbondale Highway, Eynon, PA - A Westinghouse FDP365 - 400A, 600V Hardware Overcurrent Switch Unit not listed or marked "SWD" was used by employees on a daily basis to operate the warehouse lighting circuit (277-volt fluorescent lights) exposing the employees to the hazards of an arc flash, as observed on or about December 21, 2017. In accordance with 29 CFR 1903.19, abatement certification is required for this violation.