OSHA Inspection: NATIONAL OCEANIC AND ATMOSPHERIC ADMINISTRATION-NATIONAL WEATHER SERVICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NATIONAL OCEANIC AND ATMOSPHERIC ADMINISTRATION-NATIONAL WEATHER SERVICE in 9607 NW BEAVER DRIVE, JOHNSTON, IA 50131 (NAICS 541990). OSHA activity number 342852506.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Oceanic and Atmospheric Administration-National Weather Service — free Get an email when a new federal OSHA severe-injury report for National Oceanic and Atmospheric Administration-National Weather Service is published. One employer, no account, unsubscribe in one click.
Site address
9607 NW BEAVER DRIVE
City
JOHNSTON
State
IA
ZIP
50131
Mailing
9607 NW BEAVER DRIVE, JOHNSTON, IA 50131
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541990
Employees
24
Ownership type
D

12 citations on file for this inspection.

1910.37 A02

Serious Gravity 5 1 instance 3 exposed
Issued
May 11, 2018
Abate by
Jun 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(2):  Exit routes were not arranged so that employees did not have to travel toward a high hazard area, without the path of travel being effectively shielded from the high hazard area by suitable partitions or other physical barriers:  A flammable storage cabinet was stored directly next to the door exiting the generator house.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 D05 I

Serious Gravity 5 1 instance 3 exposed
Issued
May 11, 2018
Abate by
Jun 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(5)(I): "Storage inside building" - "Egress." Flammable liquids, including stock for sale, shall not be stored so as to limit use of exits, stairways, or areas normally used for the safe egress of people:  In the storage building, the flammable storage cabinet was stored directly next to the door to exit the building.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 D07 I

Serious Gravity 5 1 instance 3 exposed
Issued
May 11, 2018
Abate by
Jun 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(7)(i): ""Extinguishers."" Suitable fire control devices, such as small hose or portable fire extinguishers, were not available at locations where flammable liquids were stored:  A suitable fire control device was not available at the flammable storage cabinet location next to the generator housing door.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.120 Q06

Deleted Serious Gravity 5 1 instance 3 exposed
Issued
May 11, 2018
Abate by
Jun 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.120(q)(6):  Training shall be based on the duties and function to be performed by each responder of an emergency response organization. The skill and knowledge levels required for all new responders, those hired after the effective date of this standard, shall be conveyed to them through training before they are permitted to take part in actual emergency operations on an incident. Employees who participate, or are expected to participate, in emergency response, shall be given training in accordance with paragraphs 1910.120(q)(6)(i) - 1910.120(q)(6)(iii):  The employer did not train and so certify that employees who participate, or are expected to participate, in emergency response, were trained in accordance with the applicable portions of paragraphs 1910.120(q)(6)(i) - 1910.120(q)(6)(iii).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.132 F01 I

Serious Gravity 10 2 instances 3 exposed
Issued
May 11, 2018
Abate by
Jun 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.132(f)(1)(i): The employer did not provide training to each employee who is required by this section to use PPE on knowing when PPE is necessary:  a)  Employees did not know to use personal protective equipment while inspecting energized, high voltage components of the UPS panel in the main facility.    b)  Employees did not know to use protective equipment while inspecting energized, high voltage components of the UPS panel at the radar site.      Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos, which you believe will be helpful.  The abatement certification sheet is enclosed with the notice(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C04 II

Deleted Serious Gravity 5 30 instances 3 exposed
Issued
May 11, 2018
Abate by
Jun 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(4)(ii): The procedures shall clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, paragraphs 1910.147(c)(4)(ii)(A) - 1910.147(c)(4)(ii)(D):  The energy control procedures did not outline:  1.  A specific statement of the intended use of the procedure.    2.  Specific procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy.    3.  Specific procedural steps for the placement, removal and transfer of lockout devices or tagout devices and the responsibility for them; and    4.  Specific requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control measures.  An example includes the 280 Volt Power Supply UD3A2 Removal Procedure in the NWS EHB 6-511:  5.3.5 280 VOLT POWER SUPPLY UD3A2.    The following procedures describe how to remove and install 280 Volt Power Supply A2. Related alignment and performance test procedures are also referenced. See Figure FO11-13, Sheet 2, view A and locate 280 Volt Power Supply A2.    Two technicians are required for this procedure.    5.3.5.1 Equipment and Tools Required.    1. Screwdriver set, flat-tip    5.3.5.2 Initial Conditions/Preliminary Setup.    WARNING    Hazardous voltages are present within the transmitter cabinet. Take all standard precautions against electric shock. Failure to comply may cause serious injury or DEATH.    1. Perform paragraph 3.4.1.2, steps 1 through 4 to power down the transmitter, lock HIGH VOLTAGE POWER CB1 circuit breaker, and remove the key.    WARNING    HIGH VOLTAGE    Filter Capacitor Bank A9 can hold a lethal charge long after transmitter power has been removed. Discharge Filter Capacitor Bank A9 after transmitter power is off and prior to transmitter maintenance by opening the right bay inner door while monitoring the charge on VOLTAGE/CURRENT Meter A1M4, at position 6, +280 VDC power supply. Opening the right bay inner door releases the filter capacitor bank discharge plunger. Failure to comply may cause serious injury or DEATH.    2. Use interlock key to unlock and open right bay inner door to discharge residual high voltage from Filter Capacitor Bank A9.    3. Use interlock key to unlock and open left bay inner door.    5.3.5.3 280 Volt Power Supply UD3A2 Removal Procedure. See Figure FO11-13, Sheet 2 and Figure FO11-13, Sheet 5, detail G and proceed as follows: 1. Disconnect cable from A2J1 on front of 280 Volt Power Supply A2.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C06 I

Serious Gravity 5 30 instances 3 exposed
Issued
May 11, 2018
Abate by
Jun 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(i): The employer shall conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirements of this standard are being followed:  The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirements of this standard were being followed.  An example of a procedure not in accordance with the requirements of this standard includes the procedure for the 280 Volt Power Supply UD3A2 Removal Procedure in the NWS EHB 6-511.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.157 E03

Serious Gravity 5 10 instances 24 exposed
Issued
May 11, 2018
Abate by
Jun 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): The employer shall assure that portable fire extinguishers are subjected to an annual maintenance check. Stored pressure extinguishers do not require an internal examination. The employer shall record the annual maintenance date and retain this record for one year after the last entry or the life of the shell, whichever is less. The record shall be available to the Assistant Secretary upon request:  Portable fire extinguishers at the facility and radar site were not subjected to an annual maintenance check.  As of April 2018, the last check was March of 2017.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01

Serious Gravity 1 1 instance 3 exposed
Issued
May 11, 2018
Abate by
Jun 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment:  The space around the transformer in the storage building was filled with equipment and supplies.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 A01

Serious Gravity 10 2 instances 3 exposed
Issued
May 11, 2018
Abate by
Jun 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a)(1): "Deenergized parts." Live parts to which an employee may be exposed was not deenergized before the employee worked on or near them:    a)  The high voltage UPS panel in the main facility was not deenergized prior to employees working near the panel.  b)  The high voltage UPS panel at the radar site was not deenergized prior to employees working near the panel.   Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos, which you believe will be helpful.  The abatement certification sheet is enclosed with the notice(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 10 2 instances 3 exposed
Issued
May 11, 2018
Abate by
Jul 31, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with, and did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work performed:     a)  Employees did not use protective equipment while inspecting energized, high voltage components of the UPS panel in the main facility.      b)  Employees did not use protective equipment while inspecting energized, high voltage components of the UPS panel at the radar site.        Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos, which you believe will be helpful.  The abatement certification sheet is enclosed with the notice(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 G08

Serious Gravity 5 1 instance 3 exposed
Issued
May 11, 2018
Abate by
Jun 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(q)(8):  The employer shall maintain in the workplace copies of the required safety data sheets for each hazardous chemical, and shall ensure that they are readily accessible during each work shift to employees when they are in their work area(s):    A safety data sheet was not maintained for the diesel fuel used in running the site's operations.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View National Oceanic and Atmospheric Administration-National Weather Service's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342852506.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.