Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TESLA ENERGY OPERATIONS, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of TESLA ENERGY OPERATIONS, INC. in HAMPSHIRE COLLEGE 893 WEST ST., AMHERST, MA 01002 (NAICS 221114). OSHA activity number 342857455.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tesla Energy Operations, INC. — free Get an email when a new federal OSHA severe-injury report for Tesla Energy Operations, INC. is published. One employer, no account, unsubscribe in one click.
Site address
HAMPSHIRE COLLEGE 893 WEST ST.
City
AMHERST
State
MA
ZIP
01002
Mailing
24 ST. MARTIN DR. BLDG. 2 UNIT 11, MARLBOROUGH, MA 01752
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221114
Employees
99
Ownership type
A

9 citations on file for this inspection.

1910.137 B01

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Apr 17, 2018
Abate by
Jun 25, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.269(a)(2)(ii)(C): Each employee were not trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments.    Tesla, Inc., Hampshire College MV Meter Cabinet, 893 West St., Amherst, Massachusetts; On or before February 1, 2018, employees were not trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments. 29 CFR 1910.137(b)(1): The employer did not provide insulating equipment for the protection of employees that was capable of withstanding, without failure, the voltages that may be imposed upon it.  Tesla, Inc., Hampshire College Solar Field Instrumentation and Control: On or about December 29, 2017, four employees performed work at the Hampshire College solar installations containing electrical equipment with voltages up to 13,800 volts and the employees were provided Class 0 electrically rated gloves with a maximum voltage rating of 1000 volts.
Recent events (3)
  • — F (S) $12934
  • — C (S) $12934
  • — Z (S) $12934

1910.269 A02 VIII

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 17, 2018
Abate by
Dec 23, 2019
Penalty
Initial $0 · Current $12,934
29 CFR 1910.269(a)(2)(viii): The employer did not ensure that each employee has demonstrated proficiency in the work practices involved before that employee is considered as having completed the training required by paragraph (a)(2) of this section.    Tesla, Inc., 24 St. Martin Dr., Marlborough, Massachusetts; On or before December 29, 2018, the employer did not ensure that each employee had demonstrated proficiency in the work practices involved before the employee is considered as having completed the training required by paragraph (a)(2) of this section.
Recent events (3)
  • — F (S) $12934
  • — C (S) $0
  • — Z (S) $0

1910.269 D02 III

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Apr 17, 2018
Abate by
May 4, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.269(d)(2)(iii): Procedures were not developed, documented, and used for the control of potentially hazardous energy covered by paragraph (d) of this section:  Tesla, Inc., Hampshire College MV Metering Panel, Amherst, Massachusetts; On or about December 29, 2017, employees were exposed to 13,800 volts while entering an energized panel to take pictures of the current transformers without utilizing the hazardous energy control procedure for the equipment.
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

1910.269 D02 V A

Deleted Serious Gravity 5 1 instance 4 exposed
Issued
Apr 17, 2018
Abate by
Jul 17, 2018
Penalty
Initial $7,391 · Current $0 Reduced
29 CFR 1910.269(d)(2)(v)(A): The employer did not complete periodic inspections, at least annually, by authorized employees who were not using the energy control procedures being inspected.  Tesla, Inc., 24 St. Martin Dr., Marlborough, Massachusetts; On or about December 29, 2017, the employer did not complete periodic inspections of the energy control procedures at least annually, by authorized personnel, to determine if there were any deficiencies in the procedures.
Recent events (3)
  • — F (S) $0
  • — C (S) $7391
  • — Z (S) $7391

1910.269 L03 III

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Apr 17, 2018
Abate by
May 4, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.269(l)(3)(iii): The employer did not ensure that no employee approached or took any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless provisions described in (l) (3) (iii) (A) - (C) were followed:   Tesla, Inc., Hampshire College MV Meter Cabinet, 893 West St., Amherst, Massachusetts; On or about December 29, 2017 an employee took conductive objects, including a cell phone, a Bluetooth headset and a wristwatch, within the minimum approach distance when entering the MV Meter Cabinet.
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

1910.269 L08 I

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Apr 17, 2018
Abate by
Apr 27, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.269(l)(8)(i): The employer shall assess the workplace to identify employees exposed to hazards from flames or from electric arcs.  (A)  The employer did not assess the workplace as required.  Tesla, Inc., Hampshire College, MV Meter Cabinet, 893 West St., Amherst, Massachusetts; On or about December 29, 2017, an employee entered the MV Meter Cabinet to take pictures of the information on current transformers without the equipment being assessed for arc hazards.
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

1910.269 L08 III

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Apr 17, 2018
Abate by
May 11, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.269(l)(8)(iii): 29 CFR 1910.269(I)(8)(v): The employer failed to ensure that each employee exposed to electric arc hazards wears protective clothing with an arc rating designed to provide the necessary protection.  Tesla, Inc., MV Meter Center, Hampshire College, 893 West St., Amherst, Massachusetts; On or about December 29, 2017, Tesla, Inc., did not ensure an employee, who was exposed to an electric arc hazard, was protected with protective clothing with an arc rating designed to provide the necessary protection.  The employee wore multiple layers of poly-blend clothing for exposure to 13,800 volts.
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

1910.269 M03 VII

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Apr 17, 2018
Abate by
May 4, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.269(m)(3)(vii): The employer did not ensure the installation of protective grounds as required by paragraph (n) of this section:  Tesla, Inc., MV Meter Center, Hampshire College, 893 West St., Amherst, Massachusetts; On or about December 29, 2017, the employer did not require the installation of protective grounds prior to an employee entering an MV Meter Cabinet to prevent exposure to an electrical shock from the 13,800 volt source.
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

1910.269 V05 II

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Apr 17, 2018
Abate by
May 4, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.269(v)(5)(ii): The employer did not maintain guarding of energized parts within a compartment during operation and maintenance functions to prevent accidental contact with energized parts and to prevent dropped tools or other equipment from contacting energized parts.  Tesla, Inc., MV Meter Center, Hampshire College, 893 West St., Amherst, Massachusetts; On or about December 29, 2017 the employer did not maintain guarding of energized parts while the employee entered to take pictures with his cell phone, to prevent accidental contact with energized parts.
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

View Tesla Energy Operations, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342857455.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.