BRISTOL, CT —
OSHA Inspection: IDEX HEALTH & SCIENCE LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of IDEX HEALTH & SCIENCE LLC in 110 HALCYON DRIVE, BRISTOL, CT 06010 (NAICS 326199). OSHA activity number 342875721.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- IDEX HEALTH & SCIENCE LLC
- Site address
- 110 HALCYON DRIVE
- City
- BRISTOL
- State
- CT
- ZIP
- 06010
- Mailing
- 110 HALCYON DRIVE, BRISTOL, CT 06010
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 120
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.37 B04
- Issued
- May 16, 2018
- Penalty
- Initial $3,534 · Current $2,474 Reduced
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent: Plant-wide: On, or about, January 11, 2018, the size and configuration of machining centers and the installation of plastic curtains blocked the line of sight for employees to see exit doors and signs. Directional signage was not provided to direct occupants to the exit routes in the plant.
Recent events (2)
- — I (S) $2473.8
- — Z (S) $3534
1910.215 A02
- Issued
- May 16, 2018
- Penalty
- Initial $3,534 · Current $2,474 Reduced
General-duty citation text
29 CFR 1910.215(a)(2): Abrasive wheel(s) used on grinding machinery were not provided with safety guard(s) which covered the spindle end, nut, flange projections: Tool Room: On, or about, January 11, 2018, the hood guard provided on the Micromaster 618 surface grinder did not cover the spindle, nut and flange projections.
Recent events (2)
- — I (S) $2473.8
- — Z (S) $3534
1910.215 B05
- Issued
- May 16, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(5): The angular exposure of grinding wheel periphery and sides for safety guards used on surface grinding machine(s) employing the wheel periphery exceeded 150 degrees: Tool Room: On, or about, January 11, 2018, approximately 180 degrees of the abrasive wheel mounted on the Mircromaster 618 surface grinder was exposed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.242 B
- Issued
- May 16, 2018
- Penalty
- Initial $3,534 · Current $2,474 Reduced
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: Tool Room: On, or about, January 11, 2018, compressed air nozzles used at the following vertical milling machines were measured to be greater than 30 p.s.i., dead-ended: A. Trak K3. B. Bridgeport, serial number J305412.
Recent events (2)
- — I (S) $2473.8
- — Z (S) $3534
1910.303 G01 I C
- Issued
- May 16, 2018
- Abate by
- Jul 3, 2018
- Penalty
- Initial $4,157 · Current $2,910 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i)(C): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, other equipment associated with the electric installation and located above or below the electric equipment extended more than 153 mm (6 inches) beyond the front of the equipment: IF Electrical Room: on, or about, January 11, 2018, transformers were installed in the working space in front of two General Electric panelboards, both labeled as LPA.
Recent events (2)
- — I (S) $2909.9
- — Z (S) $4157
1910.332 B01
- Issued
- May 16, 2018
- Abate by
- Jul 3, 2018
- Penalty
- Initial $6,929 · Current $4,850 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: Plant: On, or about, January 11, 2018, maintenance personnel had not been trained regarding what work practices and protective equipment was required to protect them against electric shock, arc flash and arc blast hazards while performing live trouble-shooting and verifying whether or not electrical equipment was properly de-energized.
Recent events (2)
- — I (S) $4850.3
- — Z (S) $6929
1910.333 C08
- Issued
- May 16, 2018
- Abate by
- Jul 3, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(c)(8): Conductive articles of jewelry and clothing (such a watch bands, bracelets, rings, key chains, necklaces, metalized aprons, cloth with conductive thread, or metal headgear) was worn where employees might contact exposed energized parts: Plant: On, or about, January 11, 2018, diagnostic testing was conducted by maintenance personnel while wearing conductive jewelry.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- May 16, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: Plant: On, or about, January 11, 2018, personal protective equipment such as, but not limited to, voltage rated gloves, fire resistive clothing, face shields, fire resistive balaclavas, hard hats and hearing protection were not provided to employees who performed live electrical work, including trouble-shooting, or who verified that electrical equipment was properly de-energized.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.22 A01
- Issued
- May 16, 2018
- Abate by
- Jul 3, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, service rooms, and walking-working surfaces were not kept in a clean, orderly, and sanitary condition: IF Electrical Room: On, or about, January 11, 2018, housekeeping practices in the electrical room were poor. Items such as, but not limited to, hot plates, tools, unused equipment, dish strainers, paint cans and boxes were stored on the floor and on electrical equipment. Also, access to the sprinkler main was blocked.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Idex Health & Science LLC
View Idex Health & Science LLC's full OSHA safety record →
More inspections in this industry (NAICS 326199)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342875721.