MARSTON, MO —
OSHA Inspection: ASSOCIATED ELECTRIC
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of ASSOCIATED ELECTRIC in 41 ST. JUDE PARK, MARSTON, MO 63866 (NAICS 221112). OSHA activity number 342881034.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ASSOCIATED ELECTRIC
- Site address
- 41 ST. JUDE PARK
- City
- MARSTON
- State
- MO
- ZIP
- 63866
- Mailing
- P.O. BOX 156, NEW MADRID, MO 63869
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221112
- Employees
- 200
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.111 B09 IX
- Issued
- Jun 5, 2018
- Abate by
- Jun 29, 2018
- Penalty
- Initial $8,638 · Current $6,250 Reduced
0170
General-duty citation text
29 CFR 1910.111(b)(9)(ix): A hydrostatic relief valve was not installed between each pair of valves in the liquid ammonia piping or hose where liquid could be trapped so as to relieve into the atmosphere at a safe location: At the time of the inspection, each hydrostatic relief valve was installed with a ball valve before the relief valve which would not allow the trapped liquid to release if the ball valve was closed. Industry practice does not allow the placement of valves inline before a pressure relief device. Abatement certification and abatement documentation is required for this violation. The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful. The abatement certification sheet is enclosed with the citations.
Recent events (3)
- — J (O) $6250
- — C (S) $8638
- — Z (S) $8638
1910.119 E03 IV
- Issued
- Jun 5, 2018
- Abate by
- Jun 29, 2018
- Penalty
- Initial $8,638 · Current $6,250 Reduced
0170
General-duty citation text
29 CFR 1910.119(e)(3)(iv): The process hazard analysis did not address the consequences of failure of engineering and administrative controls: At the time of the inspection, the most recent PHA from 11/20/2014 did not address the consequences of failure of pressure relief devices that had ball valves installed inline in front of the relief devices. The PHA did not address the administrative control of requiring employees to keep the valves in the open position to prevent the failure of piping if the relief device was blocked. Abatement certification and abatement documentation is required for this violation. The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful. The abatement certification sheet is enclosed with the citations.
Recent events (3)
- — J (O) $6250
- — C (S) $8638
- — Z (S) $8638
1910.119 H02 II
- Issued
- Jun 5, 2018
- Abate by
- Jun 29, 2018
- Penalty
- Initial $8,638 · Current $0 Reduced
0170
General-duty citation text
29 CFR 1910.119(h)(2)(ii): The employer did not inform contract employers of the known potential fire, explosion, or toxic release hazards related to the contractor's work and the process: At the time of the inspection, Security Contractor "Whelan" employees were not trained on what procedures they would follow if there was a large Ammonia release. The employer Emergency Action Plan did not supply clear policy for actions to be taken by security. Abatement certification and abatement documentation is required for this violation. The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful. The abatement certification sheet is enclosed with the citations.
Recent events (3)
- — J (S) $0
- — C (S) $8638
- — Z (S) $8638
1910.1200 F06 II
- Issued
- Jun 5, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(f)(6)(ii): Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the product identifier and words, pictures, symbols, or combination thereof, which provide at least general information regarding the hazards of the chemicals and which, in conjunction with the other information immediately available to employees under the hazard communication program, would provide employees with the specific information regarding the physical and health hazards of the hazardous chemical. At the time of the inspection, Anhydrous Ammonia storage tanks were not labeled with the hazards of the chemical.
Recent events (3)
- — J (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at Associated Electric
View Associated Electric's full OSHA safety record →
More inspections in this industry (NAICS 221112)
More inspections in MO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342881034.