PAINESVILLE, OH —
OSHA Inspection: ACCURATE METAL MACHINING, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of ACCURATE METAL MACHINING, INC. in 882 CALLENDAR BLVD, PAINESVILLE, OH 44077 (NAICS 332710). OSHA activity number 342902889.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ACCURATE METAL MACHINING, INC.
- Site address
- 882 CALLENDAR BLVD
- City
- PAINESVILLE
- State
- OH
- ZIP
- 44077
- Mailing
- 882 CALLENDAR BLVD, PAINESVILLE, OH 44077
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332710
- Employees
- 187
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.151 C
- Issued
- Mar 7, 2018
- Abate by
- Mar 13, 2018
- Penalty
- Initial $8,315 · Current $5,821 Reduced
General-duty citation text
29 CFR 1910.151(c): Where the eyes or body of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use: On or about January 26, 2018, in the water treatment tank area there was no eye wash in the immediate vicinity with unimpeded access, i.e. adjacent to the operation, where workers are required to add caustic soda (pH of 14 per SDS) to the tanks for pH control.
Recent events (2)
- — I (S) $5820.5
- — Z (S) $8315
1910.303 G01
- Issued
- Mar 7, 2018
- Abate by
- Mar 13, 2018
- Penalty
- Initial $4,989 · Current $3,492 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment: On or about January 26, 2018, the live electrical panels located on the wall directly next to the waste water storage tanks room, under the staircase, were blocked by several barrels of chemicals and fencing equipment, impeding the ready access in the event of an emergency.
Recent events (2)
- — I (S) $3492.3
- — Z (S) $4989
1910.132 D02
- Issued
- Mar 7, 2018
- Abate by
- Mar 27, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(d)(2): The required workplace hazard assessment was not certified as being performed, identifying the person completing the assessment, and written certification of the date of the assessment: On or about January 26, 2018 the workplace assessment, designed to identify personal protective equipment (PPE) needed by employees to prevent injury, was not fully performed as required. NOTE: The assessment shall be written, titled, dated and certified by signature. The required documented training shall include the following: 1) When PPE is necessary; 2) What PPE is necessary; 3) Limitations of the PPE; 4) How to properly wear and use the PPE, and 5) Inspection and care of the PPE
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.134 C01
- Issued
- Mar 7, 2018
- Abate by
- Mar 13, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.134(c)(1): The employer did not established and implemented a written respiratory protection program with worksite specific procedures: On or about January 26, 2018, the employer had not established a written respiratory program as required for the affected employees that have access to the half-mask negative air respirator available in the personal protective equipment storage locker.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.178 L04 III
- Issued
- Mar 7, 2018
- Abate by
- Apr 11, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operators performance was not conducted at least once every three years: On or about January 26, 2018, the employer had not conducted a reevaluation of the fork truck operators in the facility as required since the last training/evaluation was conducted in 2013 and 2014.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Accurate Metal Machining, INC.
View Accurate Metal Machining, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 332710)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342902889.